GENERAL

Cooper Power Systems’ RTE

®

sectionalizing switches

are used in underground residential applications with
loop feed, and in three-phase commercial industrial
installations where the ability to use an alternative source
of power is necessary. They can also be used to switch
on and off a primary cable tap on a transformer.

RTE sectionalizing switches rotate 360° in either

direction for alternate source selection. A spring-loaded
activating mechanism ensures quick loadbreak action
and positive contact engagement through all positions.

The under-oil switch can be installed near the

transformer core/coil assembly, thus minimizing cable
capacitance. With cable capacitance minimized and all
three phases switched simultaneously, the likelihood of
ferroresonance is greatly reduced. Sidewall or cover
mounted switches are hotstick operable and available in
six different blade configurations for one, two or three
pole connections.

ELECTRICAL RATINGS

TABLE 1
Voltage Ratings and Characteristics

TABLE 2
Current Ratings and Characteristics

Loadbreak/Loadmake tested per ANSI/IEEE C37.71.

OEM Equipment

Sectionalizing Switch
Installation Instructions

S800-64-1

Service Information

January 1994 • New Issue • © 1993 Cooper Power Systems, Inc.

Printed in U.S.A.

1

Description

15 kV

25 kV

35 kV

Standard Voltage Class

15

25

35

Maximum Rating Phase-to-Phase

15

25

35

Maximum Rating Phase-to-Ground

8.3 

15.2

21.1

ac 60 Hz 1 Minute Withstand

34

40

50

BIL and Full Wave Crest

95

125

150

CAUTION: Sectionalizing Switch should 
be installed only by personnel familiar

with good safety practice and the handling of
high-voltage electrical equipment.

Figure 1.
Line illustration of Sectionalizing Switch.

Description

15 kV

25 kV

35 kV

Continuous

600

300

200

Momentary, 10 Cyc. Symmetrical

10,000

10,000

10,000

Two Second, Symmetrical

10,000

10,000

10,000

3-Shot Make and Latch, Symmetrical

10,000

10,000

6,000

Loadbreak/Loadmake 

20 operations

600

300

200

30 operations

300

150

100

10 operations

100

50

25

No. Mechanical Switching Operations

Over

Over

Over

1000

1000

1000

These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide
directions for meeting every contingency during installation, operation, or maintenance. When additional information is desired to
satisfy a problem not covered sufficiently for the user’s purpose, please contact your Cooper Power Systems sales engineer.