Manual motor starters up to 25A, GHG 635
1.4
Maximum rating current for short-circuit back-up fuse for max. 50 kA, if Icc > Ics *
Short circuit protection and max. back-up fuse
Setting range
240 V AC
400V AC
500V AC
690V AC
Ics
gL, gG
Ics
gL, gG
Ics
gL, gG
Ics
gL, gG
0.10 A
......... 0.16 A
0.16 A
......... 0.25 A
0.25 A
......... 0.40 A
0.40 A
......... 0.63 A
Short circuit proof
0.63 A
......... 1.00 A
1.00 A
......... 1.60 A
no back-up fuse required, up to Icc = 50 kA
1.60 A
......... 2.50 A
40 kA 25A
2.50 A
......... 4.00 A
10 kA 40A
4.00 A
......... 6.30 A
40 kA 50A
7 kA 40A
6.30 A
......... 9.00 A
30 kA 80A
5 kA 50A
9.00 A
......... 12.50 A
27 kA 80A
4.5 kA 50A
12.50 A
......... 16.00 A
25 kA 100A
4 kA 50A
16.00 A
......... 20.00 A
22 kA 100A
3.5 kA 50A
20.00 A
......... 25.00 A
20 kA 125A
3 kA 50A
1.5
Maximum rating current for short-circuit back-up fuse for max. 100 kA, if Icc > Ics *
Short circuit protection and max. back-up fuse
Setting range
240 V AC
400V AC
500V AC
690V AC
Ics
gL, gG
Ics
gL, gG
Ics
gL, gG
Ics
gL, gG
0.10 A
......... 0.16 A
0.16 A
......... 0.25 A
0.25 A
......... 0.40 A
0.40 A
......... 0.63 A
Short circuit proof
0.63 A
......... 1.00 A
1.00 A
......... 1.60 A
no back-up fuse required, up to Icc = 100 kA
1.60 A
......... 2.50 A
40 kA 25A
2.50 A
......... 4.00 A
60 kA 35 / 40A
10 kA 40A
4.00 A
......... 6.30 A
40 kA 50A
7 kA 40A
6.30 A
......... 9.00 A
30 kA 80A
5 kA 50A
9.00 A
......... 12.50 A
75 kA 80A
27 kA 80A
4.5 kA 50A
12.50 A
......... 16.00 A
60 kA 100A
25 kA 100A
4 kA 50A
16.00 A
......... 20.00 A
55 kA 100A
22 kA 100A
3.5 kA 50A
20.00 A
......... 25.00 A
50 kA 125A
20 kA 125A
3 kA 50A
1.6
Temperature class and conductor cross-section
Setting range
Temperature class
Min. conductor cross-section
Input
Output
0.10 A
......... 1.60 A
T 6
0.75 mm²
0.75 mm²
1.60 A
......... 2.50 A
T 6
1.00 mm²
1.00 mm²
2.50 A
......... 4.00 A
T 6
1.00 mm²
1.50 mm²
4.00 A
......... 9.00 A
T 6
1.50 mm²
1.50 mm²
9.00 A
......... 12.50 A
T 6
2.50 mm²
2.50 mm²
12.50 A
......... 20.00 A
T 5
2.50 mm²
2.50 mm²
20.00 A
......... 25.00 A
T 5
4.00 mm²
4.00 mm²
*
Icc = prospective short-circuit current at installation location
Ics = Rated short-circuit breaking capacity