4. Checkout
The following is the checkout procedure to insure proper operation. If any steps in the checkout procedure produce
a yellow SYSTEM TROUBLE or AC TROUBLE LED on the keypad (See Figure 3), and an audible tone on the
SP40S
circuit board, refer to Chapter 8 “Troubleshooting” in the Installation, Testing, Operation and Maintenance
Manual. To turn off the tone, momentarily depress the “Trouble Silence” pushbutton on the keypad.
1.
Using the push on / push off buttons
on the keypad, push on the button that
corresponds to the message(s) selected
on the PC board. Push off the button to
stop the message.
2. Test the microphone circuit by
removing the microphone from its
holder and speaking into it while
depressing the push to talk button.
(For best results hold the microphone
within one-half inch from your mouth.)
3. Initiate each selected digital message
at the remote source, such as the
FACP, and verify operation.
4. Close the dead front panel and
close the front cover.
STROBE
ACTIVE
ALARM
ACTIVE
AC
TROUBLE
SYSTEM
TROUBLE
TROUBLE
SILENCE
RECORD
POWER ON
MESSAGES
Fire (Do not use elevators)
Male Voice
Fire (Do not use elevators)
Female Voice
Fire
Male Voice
Emergency
Male Voice
Emergency
Female Voice
Weather
Male Voice
All Clear
Male Voice
Test
Male Voice
Figure 3
5. Congratulations
Congratulations! You have now completed the basic installation of the
SP40S
or
SP40SE
Panel. We trust it will
give you years of trouble free operation. Should a problem arise, refer to your Installation, Testing, Operation and
Maintenance Manual. If problems persist, contact the Technical Support Engineering Department at Cooper
Wheelock Inc. (800) 631-2148.