3.  Connect conduit fittings and conduit to the Panel through the conduit entrances shown on Figure 1 as 

necessary. 

Wire the Power input on the left bottom of the Panel, and input and output wiring on the right 

side of the Panel. 

4.  Install field wiring in conduit as required. 
5.  Connect the Panel to earth ground at grounding stud shown on Figure 1. 
6.  Make sure that all debris is cleared from the enclosure.  
7.  For more details refer to Chapter 3 of the 

SP40S or SP40SE

 Installation, Testing, Operation and Maintenance 

Manual. 

 

 

2

3. Wiring 

 

The terminal blocks on the SP40S/E are removable. Lift the terminal block from the circuit 
board, attach wires to the desired connections, and then plug the terminal block back on 
the board.  

 
 

Table 1 Standard Messages for the SP40S/SP40SE 

Message   

Priority 

`Type of 
Message 

Voice 

Type 

                                                                       

Message Script 

 

Pre-Tone 

 

Post Tone 

Fire (do not use 

elevators) 

Male 

“May I have your attention please! A fire emergency has been 
reported in the building. While this is being verified, please leave 
the building by the nearest exit. Do not use the elevators.” 

Three (3) 
rounds of 

code 3 tone 

Three (3) 

rounds of 

code 3 tone 

IN2 

Fire (do not use 

elevators) 

Female 

“May I have your attention please! A fire emergency has been 
reported in the building. While this is being verified, please leave 
the building by the nearest exit. Do not use the elevators.” 

Three (3) 
rounds of 

code 3 tone 

Three (3) 

rounds of 

code 3 tone 

IN3 

Fire 

Male 

“May I have your attention please! A fire emergency has been 
reported in the building. While this is being verified, please leave 
the building by the nearest exit.” 

Three (3) 
rounds of 

code 3 tone 

Three (3) 

rounds of 

code 3 tone 

IN4 

Emergency 

Female 

“May I have your attention please! An emergency has been reported 
in the building. While this is being verified, please leave the 
building and report to the designated assembly are for your group.” 

Three (3) 
rounds of 

code 3 tone 

Three (3) 

rounds of 

code 3 tone 

IN5 

Emergency 

Male 

“May I have your attention please! An emergency has been reported 
in the building. While this is being verified, please leave the 
building and report to the designated assembly are for your group.” 

Three (3) 
rounds of 

code 3 tone 

Three (3) 

rounds of 

code 3 tone 

IN6 

Weather 

Male 

“May I have your attention please! The National Weather Service 
has issued a severe weather warning for our area.” 

Eight (8) 

seconds of 

1KHz tone 

Eight (8) 

seconds of 

1KHz tone 

IN7 

All Clear 

Male 

“May I have your attention please! The building emergency has 
ended. An all clear has been given. Please resume normal activities.” 

Eight (8) 

seconds of 

1KHz tone 

Eight (8) 

seconds of 

1KHz tone 

IN8 

10 

Test 

Male 

“May I have your attention please! This is a test of the Cooper 
Wheelock evacuation system, repeat, this is only a test.” 

No Tone 

No Tone 

IN1 

 
 

ALWAYS APPLY AC POWER BEFORE CONNECTING BATTERY BACKUP. ALWAYS 
DISCONNECT BATTERY BACKUP BEFORE DISCONNECTING AC POWER. 
IMPROPER CONNECTIONS CAN CAUSE DAMAGE TO THE EQUIPMENT AND 
PERSONAL INJURY. 

 