Figure 9

 shows the locations of the switches and LED’s on the SP40/2 that

are required

for SPRM operation.

1. Set the NAC/CC switch (SW4) on the SP40/2 PC board to the CC position.
2. Set the AUX IN jumper J2 to the 1V position.
3. Remove AUX SUP jumper (W5).
4. Install  a  UL  Listed  10K  Ohm  End  of  Line  Resistor  (EOLR)  on  the  AUX  IN  of

SP40/2.

SP40S Panel

_

_

+

_

+

+

TB6

AUX

CC/NAC

24V OUT

CC/NAC

SW6

10

0V

70

V

25

V

1V

J4

AUX
  IN

AUX
SUP

JP4

SP40S

CC/NAC SWITCH SW6
PLACE IN CC POSITION

AUXILIARY INPUT SELECTION
JUMPER J4. SELECT 1V POSITION

AUXILIARY INPUT SUPERVISION
JUMPER JP4. REMOVE FOR
SUPERVISION.

Figure 10. Switch and Jumper locations on the SP40S for SPRM Operation

See Figure 10 for switch and jumper locations.

1. Set the NAC/CC Switch (SW6) on the SP40S PC board to the CC position.
2. Set the AUX IN jumper J4 to the 1V position.
3. Remove AUX SUP jumper (JP4)

Testing

1. Energize the SP40/2 or SP40S Panel. Install the backup batteries.
2. Test each pushbutton circuit to insure the SP4-LOC is operational.
3.  Insert  key  and  turned  to  the ON  position  for  the  controls  to  function.    (The  key  is

removable only in the OFF position.)

Содержание SAFEPATH4 SP4-LOC

Страница 1: ...P4 LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE INSTALLATION AND OPERATION MANUAL MASS NOTIFICATION SYSTEM Part Number P84767 Rev A Copyright 2006 Cooper Wheelock Inc All rights reserved...

Страница 2: ...2...

Страница 3: ...RM is fully supervised from the SP40 2 or SP40S panel and contains front panel LED s for remote indications of System Normal System Trouble and Alarm conditions Voice frequency response shall be 275 H...

Страница 4: ...so be used to alert against unsafe practices Safety De energize all electrical circuits and equipment associated with installing the SP4 LOC If the HVAC Pushbutton option is being added the circuit ca...

Страница 5: ...Lock Pull slam latch with 1 8 security tamper indicator installation holes PC Boards SPRM Environmental Operating Temperature 0 to 49 C 32 to 120 F Storage Temperature 20 to 70 C 4 to 158 F Humidity N...

Страница 6: ...nsions for the SP4 LOC Front Mounting COMPLY WITH ALL OF THE LATEST APPLICABLE CODES REGULATIONS LAWS STANDARDS AND GUIDELINES 1 Remove the FRONT DOOR ASSEMBLY from the backbox by removing the eight 8...

Страница 7: ...AL HVAC EMERGENCY CUTOFF PUSHBUTTON 8 32 TRUSS HEAD SCREWS FOR MOUNTING THE INNER DOOR Figure 2 Inner Door Assembly 2 Mount the backbox assembly See Figure 3 for mounting holes Insure that the orienta...

Страница 8: ...run the appropriate pushbutton and SPRM wiring into the backbox If the optional HVAC pushbutton is installed run the HVAC wiring through a separate conduit away from the push button and remote microp...

Страница 9: ...ckbox 7 If applicable mount and wire the optional HVAC Emergency Shutoff pushbutton 8 Connect the pushbutton wiring to the terminal block as shown in Figure 4 SP40 2 and Figure 5 SP40S MASS NOTIFICATI...

Страница 10: ...SP40S NOTE The SP40S inputs can be supervised by placing a 10K Ohm resistor across each pair of input terminals on the SP4 LOC terminal block and by switching ON the DIP switches on switch block SW7...

Страница 11: ...RM AUDIO STATUS CC 6 5 4 3 2 1 Figure 7 Wiring Diagram SPRM to SP40S This wiring is power limited 10 Mount the INNER DOOR to the backbox using the four 8 32 truss head screws and plastic washers 11 M...

Страница 12: ...gure 8 Front Door Layout Operating Instructions SP40 2 Panel _ _ _ TB6 AUX IN AUX CC NAC AUX IN NAC CC W5 W4 SW4 100V 70V 25V 1V AUDIO OUT AUXILIARY INPUT SELECTION JUMPER J4 SELECT 1V POSITION CC NAC...

Страница 13: ...IN CC POSITION AUXILIARY INPUT SELECTION JUMPER J4 SELECT 1V POSITION AUXILIARY INPUT SUPERVISION JUMPER JP4 REMOVE FOR SUPERVISION Figure 10 Switch and Jumper locations on the SP40S for SPRM Operati...

Страница 14: ...1 2 AND 3 4 KNOCKOUTS PROVIDED ON TOP BOTTOM AND BACK FACE SP4 LOC BACKBOX ORIENTATION LABEL 8 32 TRUSS HEAD 4 INNER PANEL MOUNTING SCREW TERMINAL STRIP AND WIRING HARNESS 1 4 DIAMETER HOLE 6 TO ACCEP...

Страница 15: ...furnished by Cooper Wheelock Inc is installed in the product The foregoing limited warranty specifically excludes any software required for the operation of or included in a product COOPER WHEELOCK IN...

Страница 16: ...ted to the price applicable to the product or part thereof which gives rise to the claim Cooper Wheelock Inc s liability on any claim of any kind shall cease immediately upon the installation in the p...

Отзывы: