background image

12

MASS NOTIFICATION

SYSTEM

1/8" SECURITY
WIRE HOLES

SLAM LATCH

#8-32 X 3/4" STUDS (8)
ON BACK OF FRONT RING

1/2" TRIM RING ON FLUSH
MOUNT MODEL FRONT RING

Figure 8. Front Door Layout

Operating Instructions:

SP40/2 Panel

_

_

+_
+

+

TB6

AUX

IN

AUX

CC/NAC

AUX IN

NAC

CC

W5

W4

SW4

100V

70V

25V

1V

AUDIO OUT

AUXILIARY INPUT SELECTION
JUMPER J4. SELECT 1V POSITION

CC/NAC SWITCH SW4
PLACE IN CC POSITION

AUXILIARY INPUT SUPERVISION
JUMPER W5. REMOVE FOR
SUPERVISION.

Figure 9. Switch locations on the SP40/2 for SPRM Operation

Содержание SAFEPATH4 SP4-LOC

Страница 1: ...P4 LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE INSTALLATION AND OPERATION MANUAL MASS NOTIFICATION SYSTEM Part Number P84767 Rev A Copyright 2006 Cooper Wheelock Inc All rights reserved...

Страница 2: ...2...

Страница 3: ...RM is fully supervised from the SP40 2 or SP40S panel and contains front panel LED s for remote indications of System Normal System Trouble and Alarm conditions Voice frequency response shall be 275 H...

Страница 4: ...so be used to alert against unsafe practices Safety De energize all electrical circuits and equipment associated with installing the SP4 LOC If the HVAC Pushbutton option is being added the circuit ca...

Страница 5: ...Lock Pull slam latch with 1 8 security tamper indicator installation holes PC Boards SPRM Environmental Operating Temperature 0 to 49 C 32 to 120 F Storage Temperature 20 to 70 C 4 to 158 F Humidity N...

Страница 6: ...nsions for the SP4 LOC Front Mounting COMPLY WITH ALL OF THE LATEST APPLICABLE CODES REGULATIONS LAWS STANDARDS AND GUIDELINES 1 Remove the FRONT DOOR ASSEMBLY from the backbox by removing the eight 8...

Страница 7: ...AL HVAC EMERGENCY CUTOFF PUSHBUTTON 8 32 TRUSS HEAD SCREWS FOR MOUNTING THE INNER DOOR Figure 2 Inner Door Assembly 2 Mount the backbox assembly See Figure 3 for mounting holes Insure that the orienta...

Страница 8: ...run the appropriate pushbutton and SPRM wiring into the backbox If the optional HVAC pushbutton is installed run the HVAC wiring through a separate conduit away from the push button and remote microp...

Страница 9: ...ckbox 7 If applicable mount and wire the optional HVAC Emergency Shutoff pushbutton 8 Connect the pushbutton wiring to the terminal block as shown in Figure 4 SP40 2 and Figure 5 SP40S MASS NOTIFICATI...

Страница 10: ...SP40S NOTE The SP40S inputs can be supervised by placing a 10K Ohm resistor across each pair of input terminals on the SP4 LOC terminal block and by switching ON the DIP switches on switch block SW7...

Страница 11: ...RM AUDIO STATUS CC 6 5 4 3 2 1 Figure 7 Wiring Diagram SPRM to SP40S This wiring is power limited 10 Mount the INNER DOOR to the backbox using the four 8 32 truss head screws and plastic washers 11 M...

Страница 12: ...gure 8 Front Door Layout Operating Instructions SP40 2 Panel _ _ _ TB6 AUX IN AUX CC NAC AUX IN NAC CC W5 W4 SW4 100V 70V 25V 1V AUDIO OUT AUXILIARY INPUT SELECTION JUMPER J4 SELECT 1V POSITION CC NAC...

Страница 13: ...IN CC POSITION AUXILIARY INPUT SELECTION JUMPER J4 SELECT 1V POSITION AUXILIARY INPUT SUPERVISION JUMPER JP4 REMOVE FOR SUPERVISION Figure 10 Switch and Jumper locations on the SP40S for SPRM Operati...

Страница 14: ...1 2 AND 3 4 KNOCKOUTS PROVIDED ON TOP BOTTOM AND BACK FACE SP4 LOC BACKBOX ORIENTATION LABEL 8 32 TRUSS HEAD 4 INNER PANEL MOUNTING SCREW TERMINAL STRIP AND WIRING HARNESS 1 4 DIAMETER HOLE 6 TO ACCEP...

Страница 15: ...furnished by Cooper Wheelock Inc is installed in the product The foregoing limited warranty specifically excludes any software required for the operation of or included in a product COOPER WHEELOCK IN...

Страница 16: ...ted to the price applicable to the product or part thereof which gives rise to the claim Cooper Wheelock Inc s liability on any claim of any kind shall cease immediately upon the installation in the p...

Отзывы: