Introduction

Service Information S280-16-1

provides installation

instructions, operation information, and testing proce-
dures for Kyle

®

single-phase, electronically controlled

VXE15 and VXE27 reclosers.

The information contained in this manual is organized
into the following major categories: 

Safety Information,

Product Information, Control Programming and
Operation, Specifications and Ratings, Dimensions and
Weights, Installation Procedure, Recloser Operation,
Testing, Accessories, and Maintenance Information

Serial Number Updates

VXE15: Serial Number 11009 and above

Include updated oil dipstick.

VXE27: Serial Number 1948 and above

Include updated oil dipstick.

VXE Control: Serial Number 7401 and above

Include ball target lockout indicator and larger cabinet.

Read This Manual First

Read and understand the contents of this manual and fol-
low all locally approved procedures and safety practices
before installing or operating this equipment.

Additional Information

These instructions cannot cover all details or variations in
the equipment, procedures, or processes described nor
provide directions for meeting every possible contin-
gency during installation, operation, or maintenance. For
additional information, please contact your Cooper
Power Systems sales representative.

Acceptance and Initial
Inspection

Each recloser is completely assembled, tested, and
inspected at the factory. It is carefully calibrated, adjust-
ed, and filled to the correct level with insulating oil.
Always verify the proper oil level by using the dipstick
(refer to Figure 8).

It is in good condition when accepted by the carrier for
shipment. Upon receipt, inspect the recloser and the con-
trol thoroughly for damage and loss of parts or oil
incurred during shipment. If damage or loss is discov-
ered, file a claim with the carrier immediately.

Check for oil leakage and tighten all bolts that may have
loosened during shipment, especially the tank mounting
bolts. Tank mounting bolts should be tightened to 34–54
N•m (25–40 ft•lb) torque, using an alternating tightening
pattern.

Handling and Storage

Recloser and Control

If the unit is to be stored for any appreciable time before
installation, provide a clean, dry storage area. Be careful
during handling and storage to minimize the possibility of
damage; in particular, protect the bushings, control, and
control cable.

Control and Lockout Indicator
Batteries

During storage, the control and lockout indicator batteries
must be disconnected from the control and lockout indi-
cator circuit boards. If the storage area temperature
exceeds 100° F, remove the control batteries and store in
a cool, dry area.

Standards

The Kyle

®

Type VXE recloser is designed and tested in

accordance with:

ANSI/IEEE C37.60 - 1981

ANSI C37.61 - 1973

ANSI C37.85 - 1989

Quality Standards

ISO 9001:2000 Certified Quality Management System

Description

The Type VXE recloser is a self-contained, single-phase,
current-interrupting device. VXE reclosers protect distrib-
ution systems with phase-to-phase voltage ratings of
15.5 through 27.0 kV and are rated at 400 A maximum
continuous current and 8000 A symmetrical interrupting
current.

A complete Type VXE recloser assembly consists of a
VXE recloser and a separate VXE control, which is con-
nected to the recloser with a control cable. The control
cable is available in lengths from 2–30 m (7–100 ft) and
is specified at time of order. The control cabinet is
designed to be mounted to the recloser tank, or it can be
mounted to the pole or other mounting structure, such as
crossarms, at a distance equal to the cable length. The
control cable is attached to the control and recloser with
threaded, separable weatherproof connectors.

S280-16-1

3

!

SAFETY

FOR LIFE

PRODUCT INFORMATION

Содержание VXE Control

Страница 1: ...rogramming and Operation 7 Type VXE Electronic Control 7 Programming the Control Settings 8 Specifications and Ratings 10 Dimensions 11 Installation Procedure 12 Placing the Recloser In Service 13 Ope...

Страница 2: ...ting main taining or testing this equipment carefully read and understand the contents of this manual Improper operation handling or maintenance can result in death severe personal injury and equipmen...

Страница 3: ...ss is discov ered file a claim with the carrier immediately Check for oil leakage and tighten all bolts that may have loosened during shipment especially the tank mounting bolts Tank mounting bolts sh...

Страница 4: ...voltage closing is sup plied through a 2 pin connector mounted on the recloser head Closing Solenoid Operation The closing operation is illustrated by considering the recloser to be connected to the l...

Страница 5: ...ion the lever is pulled from under the sleet hood to its down position as shown in Figure 2 The lever must be manually returned to the up position in order to return the recloser to its pre programmed...

Страница 6: ...eration section of this manual for further information The VXE control can be equipped with an optional SCADA input output board to provide remote operation and status functions for SCADA applications...

Страница 7: ...pening actuator In addition a control battery is required to supply power to the control during the reclose intevals If line current drops below 3 A or the recloser is in the open position power is th...

Страница 8: ...le protecting fuses from tem porary faults Sequence Coordination is always active for the number of TCC1 operations selected for the VXE control For example for two trip operations on TCC1 and two tri...

Страница 9: ...TCC2 Time Current Curve Modifiers The DIP switches labeled S6 Figure 5 are used to mod ify the shape of the time current curve produced by the TCC plug in card for TCC1 and or TCC2 Each TCC plug in ca...

Страница 10: ...imate inches 0 4 0 5 Contact Close Time Close Signal To Contact Make seconds 0 19 0 24 Open Contact Travel Time Open Signal To Contact Part seconds 0 014 0 022 Interrupting Time Open Signal to Arc Ext...

Страница 11: ...Pole Bolt Connector NO 6 350 MCM 16 UNC 2B 8 5 Figure 6 Dimensions of Types VXE15 and VXE27 reclosers Type Bushing Type A B C VXE15 standard 1156 45 5 483 19 270 10 5 VXE15 extra creepage 1237 48 75 5...

Страница 12: ...ug as shown in Figure 4 Make sure that all DIP switch settings are set correctly and that the control cable is connected between the recloser and control 6 Mount the recloser Use the lifting lug locat...

Страница 13: ...en placing the recloser in service Be sure that the control battery is properly connected When the recloser is connected and source side high voltage lines are energized by closing the source side dis...

Страница 14: ...dle down and returning the yellow handle to its up Closed position If the VXE con trol is equipped with the optional SCADA input output accessory board the recloser can be remotely closed from lockout...

Страница 15: ...n the 600 5 tap 3 Ammeter Must have a rating based on the level of test current Since the control is responsive to peak current it is recommended that metering responsive to peak current be used when...

Страница 16: ...the pipe plug in the head casting before placing the recloser in service High Potential Insulation Level Withstand Tests High potential withstand tests provide information on the dielectric condition...

Страница 17: ...when the recloser trips and compare to the VXE control s pro grammed minimum trip value Sequence of Operation Test The operating sequence can be checked by using the manual closing tool to close the r...

Страница 18: ...ating correct operation of the clos ing solenoid Type VXE Single Phase Electronically Controlled Recloser Installation and Operation Instructions 18 Figure 13 Suggested test diagram for high voltage c...

Страница 19: ...SCADA I O board also includes dry contacts to provide remote status information All remote features are accessed through a 19 pin recep tacle Type MS 22 14 female mounted on the bottom of the control...

Страница 20: ...Department offers recloser mainte nance training classes These classes taught by experi enced service technicians are held at the factory s in house training facility For additional information contac...