Introduction
Service Information S280-16-1
provides installation
instructions, operation information, and testing proce-
dures for Kyle
®
single-phase, electronically controlled
VXE15 and VXE27 reclosers.
The information contained in this manual is organized
into the following major categories:
Safety Information,
Product Information, Control Programming and
Operation, Specifications and Ratings, Dimensions and
Weights, Installation Procedure, Recloser Operation,
Testing, Accessories, and Maintenance Information
.
Serial Number Updates
VXE15: Serial Number 11009 and above
Include updated oil dipstick.
VXE27: Serial Number 1948 and above
Include updated oil dipstick.
VXE Control: Serial Number 7401 and above
Include ball target lockout indicator and larger cabinet.
Read This Manual First
Read and understand the contents of this manual and fol-
low all locally approved procedures and safety practices
before installing or operating this equipment.
Additional Information
These instructions cannot cover all details or variations in
the equipment, procedures, or processes described nor
provide directions for meeting every possible contin-
gency during installation, operation, or maintenance. For
additional information, please contact your Cooper
Power Systems sales representative.
Acceptance and Initial
Inspection
Each recloser is completely assembled, tested, and
inspected at the factory. It is carefully calibrated, adjust-
ed, and filled to the correct level with insulating oil.
Always verify the proper oil level by using the dipstick
(refer to Figure 8).
It is in good condition when accepted by the carrier for
shipment. Upon receipt, inspect the recloser and the con-
trol thoroughly for damage and loss of parts or oil
incurred during shipment. If damage or loss is discov-
ered, file a claim with the carrier immediately.
Check for oil leakage and tighten all bolts that may have
loosened during shipment, especially the tank mounting
bolts. Tank mounting bolts should be tightened to 34–54
N•m (25–40 ft•lb) torque, using an alternating tightening
pattern.
Handling and Storage
Recloser and Control
If the unit is to be stored for any appreciable time before
installation, provide a clean, dry storage area. Be careful
during handling and storage to minimize the possibility of
damage; in particular, protect the bushings, control, and
control cable.
Control and Lockout Indicator
Batteries
During storage, the control and lockout indicator batteries
must be disconnected from the control and lockout indi-
cator circuit boards. If the storage area temperature
exceeds 100° F, remove the control batteries and store in
a cool, dry area.
Standards
The Kyle
®
Type VXE recloser is designed and tested in
accordance with:
ANSI/IEEE C37.60 - 1981
ANSI C37.61 - 1973
ANSI C37.85 - 1989
Quality Standards
ISO 9001:2000 Certified Quality Management System
Description
The Type VXE recloser is a self-contained, single-phase,
current-interrupting device. VXE reclosers protect distrib-
ution systems with phase-to-phase voltage ratings of
15.5 through 27.0 kV and are rated at 400 A maximum
continuous current and 8000 A symmetrical interrupting
current.
A complete Type VXE recloser assembly consists of a
VXE recloser and a separate VXE control, which is con-
nected to the recloser with a control cable. The control
cable is available in lengths from 2–30 m (7–100 ft) and
is specified at time of order. The control cabinet is
designed to be mounted to the recloser tank, or it can be
mounted to the pole or other mounting structure, such as
crossarms, at a distance equal to the cable length. The
control cable is attached to the control and recloser with
threaded, separable weatherproof connectors.
S280-16-1
3
!
SAFETY
FOR LIFE
PRODUCT INFORMATION