Cooper Power Systems VXE Control Скачать руководство пользователя страница 17

Open-Contacts High-Potential Test

1.

Pull down the Manual Operating Handle to open the
recloser contacts.

2

. Ground the recloser head casting, control, and load-

side bushing.

3.

Apply the proper test voltage to the source-side
bushing.

4.

The recloser should withstand the test voltage for 60
seconds.

5.

Ground the source-side bushing.

6.

Apply the proper test voltage to the load-side bushing.

7.

The recloser should withstand the test voltage for 60
seconds.

Test Results

The high-potential withstand tests provide information on
the dielectric condition of the recloser and the integrity of
the vacuum interrupter.

If the recloser passes the closed-contacts test but fails
the open-contacts test, the cause is likely to be a deteri-
oration of the vacuum interrupter. Replace the interrupter
and retest to confirm the repair.

If the recloser fails the closed-contacts test, the cause is
likely to be a diminished electrical clearance, low oil
dielectric strength, or failed insulation. After correcting
the problem, retest to confirm the repair.

Minimum-Trip Current Level Test

The minimum-trip current can be checked by using the
manual closing tool to close the recloser while it is de-
energized and then tripping the recloser with the low-voltage
ac source. Assemble and connect the low-voltage test
portion of the set-up shown in Figure 12 and proceed as
follows:

1.

With the yellow manual operating handle in the
CLOSED position, use the manual closing tool to
close the recloser.

2.

Connect the low-voltage test leads to the recloser
bushings as shown in Figure 12.

3.

Slowly increase the variable autotransformer voltage
from zero, note the ammeter reading when the
recloser trips, and compare to the VXE control’s pro-
grammed minimum-trip value.

Sequence of Operation Test

The operating sequence can be checked by using the
manual closing tool to close the recloser while it is de-
energized and then tripping the recloser with the low-
voltage ac source.

1.

Check the number of programmed fast and delayed
operations by observing the VXE control DIP switch
setting for Operations To Lockout (labeled S2) and
the number of TCC 1 fast operations programmed on
DIP switches labeled S3.

2.

Assemble and connect the low-voltage test portion of
the set-up shown in Figure 12 and proceed as follows:

3.

With the yellow manual operating handle in the
CLOSED position, use the manual closing tool to
close the recloser.

4.

Connect the low-voltage test leads to the recloser
bushings as shown in Figure 12.

5.

Using the customer supplied variable autotrans-
former, apply a test current above the minimum-trip
level to trip the recloser.  

6.

Repeat step 5 until the recloser locks out, which is
indicated by the orange control lockout indicator tar-
get on the bottom of the control cabinet. 

Test Results

Note the number of fast and delayed operations to lockout
and compare these numbers to the programmed values.

S280-16-1

17

!

SAFETY

FOR LIFE

WARNING: 

Hazardous voltage.  Never connect

a high voltage source for testing closing coil oper-

ation and a low voltage source for fault current trip
operation, simultaneously. The high- and low-voltage
circuits are not compatible. Failure to comply can result
in death, severe personal injury, and equipment damage.

T233.2

!

Figure 12.
Suggested test diagram for minimum-trip testing.

120 Vac

1

2

Clamp-on
Ammeter

NOTE: Use at
least 2/0 cable
between bushings

Variable
Autotransformer*
   (10 A)

600:5
Recloser
BCT on 600:5 Tap

This Test Circuit can
apply over 800 A
to the Recloser

*Customer Supplied.

Содержание VXE Control

Страница 1: ...rogramming and Operation 7 Type VXE Electronic Control 7 Programming the Control Settings 8 Specifications and Ratings 10 Dimensions 11 Installation Procedure 12 Placing the Recloser In Service 13 Ope...

Страница 2: ...ting main taining or testing this equipment carefully read and understand the contents of this manual Improper operation handling or maintenance can result in death severe personal injury and equipmen...

Страница 3: ...ss is discov ered file a claim with the carrier immediately Check for oil leakage and tighten all bolts that may have loosened during shipment especially the tank mounting bolts Tank mounting bolts sh...

Страница 4: ...voltage closing is sup plied through a 2 pin connector mounted on the recloser head Closing Solenoid Operation The closing operation is illustrated by considering the recloser to be connected to the l...

Страница 5: ...ion the lever is pulled from under the sleet hood to its down position as shown in Figure 2 The lever must be manually returned to the up position in order to return the recloser to its pre programmed...

Страница 6: ...eration section of this manual for further information The VXE control can be equipped with an optional SCADA input output board to provide remote operation and status functions for SCADA applications...

Страница 7: ...pening actuator In addition a control battery is required to supply power to the control during the reclose intevals If line current drops below 3 A or the recloser is in the open position power is th...

Страница 8: ...le protecting fuses from tem porary faults Sequence Coordination is always active for the number of TCC1 operations selected for the VXE control For example for two trip operations on TCC1 and two tri...

Страница 9: ...TCC2 Time Current Curve Modifiers The DIP switches labeled S6 Figure 5 are used to mod ify the shape of the time current curve produced by the TCC plug in card for TCC1 and or TCC2 Each TCC plug in ca...

Страница 10: ...imate inches 0 4 0 5 Contact Close Time Close Signal To Contact Make seconds 0 19 0 24 Open Contact Travel Time Open Signal To Contact Part seconds 0 014 0 022 Interrupting Time Open Signal to Arc Ext...

Страница 11: ...Pole Bolt Connector NO 6 350 MCM 16 UNC 2B 8 5 Figure 6 Dimensions of Types VXE15 and VXE27 reclosers Type Bushing Type A B C VXE15 standard 1156 45 5 483 19 270 10 5 VXE15 extra creepage 1237 48 75 5...

Страница 12: ...ug as shown in Figure 4 Make sure that all DIP switch settings are set correctly and that the control cable is connected between the recloser and control 6 Mount the recloser Use the lifting lug locat...

Страница 13: ...en placing the recloser in service Be sure that the control battery is properly connected When the recloser is connected and source side high voltage lines are energized by closing the source side dis...

Страница 14: ...dle down and returning the yellow handle to its up Closed position If the VXE con trol is equipped with the optional SCADA input output accessory board the recloser can be remotely closed from lockout...

Страница 15: ...n the 600 5 tap 3 Ammeter Must have a rating based on the level of test current Since the control is responsive to peak current it is recommended that metering responsive to peak current be used when...

Страница 16: ...the pipe plug in the head casting before placing the recloser in service High Potential Insulation Level Withstand Tests High potential withstand tests provide information on the dielectric condition...

Страница 17: ...when the recloser trips and compare to the VXE control s pro grammed minimum trip value Sequence of Operation Test The operating sequence can be checked by using the manual closing tool to close the r...

Страница 18: ...ating correct operation of the clos ing solenoid Type VXE Single Phase Electronically Controlled Recloser Installation and Operation Instructions 18 Figure 13 Suggested test diagram for high voltage c...

Страница 19: ...SCADA I O board also includes dry contacts to provide remote status information All remote features are accessed through a 19 pin recep tacle Type MS 22 14 female mounted on the bottom of the control...

Страница 20: ...Department offers recloser mainte nance training classes These classes taught by experi enced service technicians are held at the factory s in house training facility For additional information contac...

Отзывы: