background image

Count Reset

The count reset feature resets the sectionalizer count to
zero whenever current below the actuating level flows
through the sectionalizer for longer than the pro-
grammed reset time without interruption. The reset time
settings have a tolerance of ±10 percent.

It can be verified by interrupting an overcurrent flow
through the sectionalizer one time less than the counts-
to-open setting, then allowing load current to flow for
periods just under and just over the reset setting. The
sectionalizer should open if the overcurrent for the final
count is interrupted within the reset time period (count
has reset to zero). The following procedures may be
used to verify the count reset:

1.

Jumper the ground actuating current resistor with a
short lead to disable the ground-sensing circuit.

2.

Program the sectionalizer control for two counts-to-
open and set the COUNT RESET SELECTOR to 15
seconds.

3.

Jumper terminals P and D together.

4.

Close the sectionalizer.

5.

With test circuit connected to phase A of the section-
alizer and S1 open, close S2 and raise the test cur-
rent to slightly above the appropriate value shown in
Column B of Table 8. Hold S2 closed for at least
three seconds.

6.

Release S2 to simulate a backup protective device
clearing the overcurrent. The sectionalizer will regis-
ter a count.

7.

Close S1 for 13.5 seconds.

8.

Momentarily close and then release switch S2. The
sectionalizer 

should 

open, verifying that the count

reset has not been activated.

9.

Reclose the sectionalizer and then close and release
S2 once to register one overcurrent interruption
count.

10.

Close S1 for slightly more than 16.5 seconds.

11.

Momentarily close and release switch S2. The sec-
tionalizer 

should not 

open, verifying that the count

reset has been activated and the first count has
been erased.

12.

Again, close and release S2. The sectionalizer

should

open.

13.

Remove the jumper form terminals P and D.

Inrush-Current Restraint

The inrush-current restraint feature distinguishes
between fault currents and inrush currents. For fault cur-
rent interruptions, the sectionalizer counts and opens
normally. For an inrush-current condition, the phase and
ground minimum actuating current detection is blocked
for three seconds to prevent counting the inrush current.

The three-second time interval allows for system inrush
parameters to stabilize prior to allowing the sensitivity of
the sectionalizer to return to its programmed state.

The operation of the inrush-current restraint can be veri-
fied by simulating a fault condition (the overcurrent is
preceded by an overcurrent interruption) and an inrush
condition (the overcurrent is preceded by a load current
interruption).

The following procedure can be used to verify the
inrush-current restraint feature.

1.

Jumper the ground actuating current resistor with a
short lead to disable the ground sensing circuit.

2.

Set the COUNTS TO OPEN SELECTOR switch to 

1

.

3.

Manually close the sectionalizer.

4.

With the test circuit connected to phase A of the sec-
tionalizer and S1 open, hold S2 closed and raise the
test current to slightly below the appropriate value
shown in Column A of Table 8.

5.

Release S2 to simulate a backup opening with only
load current flowing through the sectionalizer when
current was interrupted. The sectionalizer 

should

not

open.

6.

Close S2 and in 

no more than three seconds

adjust the test current to just below twice the appro-
priate value shown in Column A of Table 8 to simu-
late an inrush condition. Release S2. The sectional-
izer 

should not 

open, verifying that the inrush

restraint feature has been activated.

7.

Reset the inrush restraint as follows:

A.

Short test terminals D and P together.

B.

Close S1 closed for 3.5 seconds.

C.

Open S1 and remove short from Test Terminals D
and P.

8.

Close S2 and raise the test current to slightly above
the appropriate value shown in Column B of Table 8.

9.

Release S2 to simulate a backup opening with fault
current flowing through the sectionalizer when cur-
rent was interrupted. The sectionalizer 

should 

open.

10.

Close the sectionalizer.

11.

Repeat step 9 to simulate a fault condition.

12.

Release S2. The sectionalizer should open verifying
that the inrush restraint has not been activated.

Post-Test Procedures

After testing has been completed, make sure that the
control settings are programmed to the operating param-
eters as originally specified.

19

S270-20-3

!

SAFETY

FOR LIFE

Содержание Kyle GV

Страница 1: ...nalizer 9 Mounting the Sectionalizer 9 Grounding the Sectionalizer 9 High Voltage Connections 11 120 Vac Wiring 11 Internal Wiring 12 Auxiliary Switch 13 Operating Instructions 15 Initial Operation 15...

Страница 2: ...this equipment carefully read and understand the contents of this manual Improper operation handling or maintenance can result in death severe personal injury and equipment damage G101 0 SAFETY FOR LI...

Страница 3: ...d keep the operator cabinet closed to protect the electronic control components Standards Kyle sectionalizers are designed and tested in accor dance with ANSI standard C37 63 where applicable Quality...

Страница 4: ...g A 400 400 Rated symmetrical interrupting current A rms 880 880 Rated making current asymmetrical A rms 20000 15000 Short time ratings A rms 10 seconds symmetrical 4000 3500 1 second symmetrical 1250...

Страница 5: ...tors No 6 solid 350 MCM 305 12 1203 47 25 435 17 329 13 562 22 Ground Connector No 8 No 2 Figure 2 Type GW Sectionalizer 254 10 203 8 Terminal Connectors No 6 solid 350 MCM Ground Connector No 8 No 2...

Страница 6: ...d an operations counter are located under the sleet hood of the operator cabinet The yellow contact position indicator is pinned to the main operating shaft of the sectionalizer to indicate the OPEN a...

Страница 7: ...phase current resis tors are listed in Table 3 Ground current resistors are identified with the ground sym bol and the actuating current value in amperes Catalog numbers for the available ground curr...

Страница 8: ...gh the sectionalizer is restored and the overcurrent has been determined to be inrush current The three second time interval allows for system inrush parameters to stabilize prior to allowing the sens...

Страница 9: ...ng height is equal to or greater than the distance between lifting lugs See Figure 8 Mounting the Sectionalizer Figures 9 and 10 show installation using Kyle mounting frames If other mounting means ar...

Страница 10: ...13 473 mm 18 5 378 mm 14 5 432 mm 17 244 mm 9 5 383 mm 15 25 324 mm 12 75 699 mm 27 5 622 mm 24 5 489 mm 19 25 508 mm 20 244 mm 9 75 383 mm 15 Figure 10 Mounting hardware for Type GV sectionalizer 62...

Страница 11: ...and the cover of the GW sectionalizers will accept No 8 through No 2 stranded wire 120 Vac Wiring A 120 Vac source voltage is required if the mechanism cabinet heater and the potential charger for th...

Страница 12: ...One Count Switch G RED YEL G C B A A C B C T Protector NC NO C Count Reset Switch Zenar Diode Zenar Diode A B C D E F 1 Potential Charger Board ORG YEL GRN WHT BLK WHT 2 4 3 Heater D B BLK WHT 120 Va...

Страница 13: ...he switch link by removing the groove pin and C rings 3 Remove the machine screws attaching the assembly to the cabinet 4 With the switch removed unfasten the two hex nuts and lockwashers from the lon...

Страница 14: ...punch mark on the shaft are in vertical plane with the punch mark in the end plate as shown TERMINALS 3 7 11 15 CAMS TERMINALS 1 5 9 13 TERMINALS 2 6 10 14 TERMINALS 4 8 12 16 CONTACTS SQUARE SHAFT CA...

Страница 15: ...e work the sectionalizer can be programmed for one count to open without opening the operator mechanism housing and disturbing the normal operating settings The one count to open lever overrides the C...

Страница 16: ...performing the following tests monitor the conti nuity between test points C and D on the circuit board see Figure 6 If no continuity exists between either set of test points upon closing of the secti...

Страница 17: ...sibility of a false count the phase sensing portion of the sectionalizer control circuit should be disabled when the ground minimum actuating current is being checked The following procedure is used 1...

Страница 18: ...lso inter rupted To check the voltage restraint feature proceed as follows 1 Jumper the ground actuating resistor with a short lead to disable the ground sensing circuit 2 Jumper terminals P and D tog...

Страница 19: ...normally For an inrush current condition the phase and ground minimum actuating current detection is blocked for three seconds to prevent counting the inrush current The three second time interval al...

Страница 20: ...y Street Pewaukee WI 53072 USA www cooperpower com 2005 Cooper Power Systems or its affiliates Kyle is a registered trademark of Cooper Power Systems or its affiliates KA2048 101 Rev 01 SAFETY FOR LIF...

Отзывы: