background image

Count Restraint

The count restraint feature prevents erroneous counts of
overcurrents interrupted by downline protective devices
by blocking the counting operation as long as a mini-
mum of 0.5 A of uninterrupted line current flows through
the sectionalizer.

The operation of the count restraint can be verified by
superimposing an interruptible overcurrent on a constant
minimum line current. The sectionalizer will not count or
open on the interruption of the overcurrent as long as
the minimum line current is not interrupted. To check the
count restraint feature, proceed as follows:

1.

Jumper the ground actuating current resistor with a
short lead to disable the ground sensing circuit.

2.

Jumper terminals P and D together.

3.

Check that the sectionalizer control is set for one-
count-to-open.

4.

Close the sectionalizer by operating the close pullring
the required number of times.

5.

With the test circuit connected to phase A of the sec-
tionalizer and S1 closed (to simulate a constant load
current of approximately 6 A), hold S2 closed and raise
the test current to slightly above the appropriate values
shown in Column B of Table 8. Hold S2 closed for at
least three seconds

6.

Release S2 to simulate a downline device clearing the
overcurrent. The sectionalizer 

should not

open verify-

ing the operation of the count restraint feature.

7.

Open S1 and again close and adjust S2 to simulate a
backup device clearing the fault. This time the section-
alizer should count the overcurrent interruption and
open.

8.

Remove the jumper from terminals P and D.

Voltage Restraint

When energized at 120 Vac, the voltage charging board
provides fast charging times for the trip energy storage
capacitors. It also acts as a voltage restraint; the sectional-
izer will not count an overcurrent interruption of the protec-
tive device unless the voltage at the control is also inter-
rupted. To check the voltage restraint feature, proceed as
follows:

1.

Jumper the ground actuating resistor with a short lead
to disable the ground sensing circuit.

2.

Jumper terminals P and D together.

3.

Program the sectionalizer for one-count-to-open.

4.

Close the sectionalizer.

5.

Connect 120 Vac across pins B and D of the 120 Vac
input receptacle.

6.

With the test circuit connected to Phase A of the sec-
tionalizer and S1 open, Close S2 and raise the current
slightly above the appropriate value shown in Column
B of Table 8. Hold S2 closed for at least three sec-
onds.

7.

Release S2 to simulate a downline device clearing the
overcurrent. The sectionalizer 

should not

open.

8.

Disconnect the 120 Vac from the input receptacle.

9.

Again close and release S2. The sectionalizer 

should

open.

10.

Remove the jumper from terminals P and D.

Number of Counts-to-Open

The number of counts-to-open can be verified by inter-
rupting, the preset number of times, an overcurrent
through the sectionalizer. For example, with the control
set for three counts, the sectionalizer will open upon the
third overcurrent interruption. Proceed as follows:

1.

Jumper the ground actuating current resistor with a
short lead to disable the ground sensing circuit.

2.

Jumper terminals P and D together.

3.

Program the sectionalizer for three counts-to-open by
setting the COUNTS-TO-OPEN SELECTOR switch to 

3.

4.

Close the sectionalizer by operating the close pullring
the required number of times.

5.

With the test circuit connected to phase A of the sec-
tionalizer and S1 open, close S2 and raise the test cur-
rent to slightly above the appropriate value shown in
Column B of Table 8. Hold S2 closed for at least three
seconds.

6.

Open and close S2 a number of times. The sectionaliz-
er should open upon the third opening of S2.

7.

To verify the two-counts-to-open setting, set the
COUNTS-TO-OPEN SELECTOR switch to 

2

and

repeat steps 3 through 5. The sectionalizer should
open upon the second opening of S2.

8.

Remove the jumper from terminals P and D.

Type GV and GW Installation Instructions

18

Содержание Kyle GV

Страница 1: ...nalizer 9 Mounting the Sectionalizer 9 Grounding the Sectionalizer 9 High Voltage Connections 11 120 Vac Wiring 11 Internal Wiring 12 Auxiliary Switch 13 Operating Instructions 15 Initial Operation 15...

Страница 2: ...this equipment carefully read and understand the contents of this manual Improper operation handling or maintenance can result in death severe personal injury and equipment damage G101 0 SAFETY FOR LI...

Страница 3: ...d keep the operator cabinet closed to protect the electronic control components Standards Kyle sectionalizers are designed and tested in accor dance with ANSI standard C37 63 where applicable Quality...

Страница 4: ...g A 400 400 Rated symmetrical interrupting current A rms 880 880 Rated making current asymmetrical A rms 20000 15000 Short time ratings A rms 10 seconds symmetrical 4000 3500 1 second symmetrical 1250...

Страница 5: ...tors No 6 solid 350 MCM 305 12 1203 47 25 435 17 329 13 562 22 Ground Connector No 8 No 2 Figure 2 Type GW Sectionalizer 254 10 203 8 Terminal Connectors No 6 solid 350 MCM Ground Connector No 8 No 2...

Страница 6: ...d an operations counter are located under the sleet hood of the operator cabinet The yellow contact position indicator is pinned to the main operating shaft of the sectionalizer to indicate the OPEN a...

Страница 7: ...phase current resis tors are listed in Table 3 Ground current resistors are identified with the ground sym bol and the actuating current value in amperes Catalog numbers for the available ground curr...

Страница 8: ...gh the sectionalizer is restored and the overcurrent has been determined to be inrush current The three second time interval allows for system inrush parameters to stabilize prior to allowing the sens...

Страница 9: ...ng height is equal to or greater than the distance between lifting lugs See Figure 8 Mounting the Sectionalizer Figures 9 and 10 show installation using Kyle mounting frames If other mounting means ar...

Страница 10: ...13 473 mm 18 5 378 mm 14 5 432 mm 17 244 mm 9 5 383 mm 15 25 324 mm 12 75 699 mm 27 5 622 mm 24 5 489 mm 19 25 508 mm 20 244 mm 9 75 383 mm 15 Figure 10 Mounting hardware for Type GV sectionalizer 62...

Страница 11: ...and the cover of the GW sectionalizers will accept No 8 through No 2 stranded wire 120 Vac Wiring A 120 Vac source voltage is required if the mechanism cabinet heater and the potential charger for th...

Страница 12: ...One Count Switch G RED YEL G C B A A C B C T Protector NC NO C Count Reset Switch Zenar Diode Zenar Diode A B C D E F 1 Potential Charger Board ORG YEL GRN WHT BLK WHT 2 4 3 Heater D B BLK WHT 120 Va...

Страница 13: ...he switch link by removing the groove pin and C rings 3 Remove the machine screws attaching the assembly to the cabinet 4 With the switch removed unfasten the two hex nuts and lockwashers from the lon...

Страница 14: ...punch mark on the shaft are in vertical plane with the punch mark in the end plate as shown TERMINALS 3 7 11 15 CAMS TERMINALS 1 5 9 13 TERMINALS 2 6 10 14 TERMINALS 4 8 12 16 CONTACTS SQUARE SHAFT CA...

Страница 15: ...e work the sectionalizer can be programmed for one count to open without opening the operator mechanism housing and disturbing the normal operating settings The one count to open lever overrides the C...

Страница 16: ...performing the following tests monitor the conti nuity between test points C and D on the circuit board see Figure 6 If no continuity exists between either set of test points upon closing of the secti...

Страница 17: ...sibility of a false count the phase sensing portion of the sectionalizer control circuit should be disabled when the ground minimum actuating current is being checked The following procedure is used 1...

Страница 18: ...lso inter rupted To check the voltage restraint feature proceed as follows 1 Jumper the ground actuating resistor with a short lead to disable the ground sensing circuit 2 Jumper terminals P and D tog...

Страница 19: ...normally For an inrush current condition the phase and ground minimum actuating current detection is blocked for three seconds to prevent counting the inrush current The three second time interval al...

Страница 20: ...y Street Pewaukee WI 53072 USA www cooperpower com 2005 Cooper Power Systems or its affiliates Kyle is a registered trademark of Cooper Power Systems or its affiliates KA2048 101 Rev 01 SAFETY FOR LIF...

Отзывы: