Set switches and jumpers on the SP40S as follows:
•
Set jumper J4 to 1V position.
•
Set SW6 to the contact closure (CC) position.
•
Remove jumper JP4 to enable supervision of the CC input wiring.
Set switches and jumpers on the SP4-RMX as follows
•
Set SW1 to the SP40 position.
•
Set Jumper J1 to 1V.
•
Set switches on switch block SW3 to the ON position for each SPRM connected. Insure the corresponding switch is OFF for any
SPRM inputs not used.
•
Set S1 switch on SW2 to the desired position according to Table 1. Set S2 to ON. Switch S3 to the ON Position.
SP40S with Two Ganged SP4-RMX Modules
AUX IN
CC/NAC
SP40S
24 VDC
10K
EOLR
10K
EOLR
10K
EOLR
10K
EOLR
S3
S2
S3
SW2
RM
3 VO
L
RM
2
VOL
RM
1
VOL
1V
25
V
70
V
AUX VO
L
R3
7
J1
S3
S2
S1
SW
2
RM
3
VOL
RM
2
VOL
RM
1
VOL
1V
25V
70V
AUX VO
L
R3
7
J1
Figure 4:
Two Ganged SP4-RMX Modules
Set switches and jumpers on the SP40S as follows:
•
Set jumper J4 to 1V position.
•
Set SW6 to the contact closure (CC) position.
•
Remove jumper JP4 to enable supervision of the CC input wiring.
Set switches and jumpers on the SP4-RMX as follows
•
Set SW1 to the SP40 position.
•
Set Jumper J1 to 1V.
•
Set switches on switch block SW3 to the ON position for each SPRM connected. Insure the corresponding switch is OFF for any
SPRM inputs not used.
•
Set switch S1 on SW2 to the desired position according to Table 1. Set S2 to ON. Switch S3 to the OFF position.