TROUBLESHOOTING: 

 
 

The SP4-RMX contain yellow LED indicators that, when illuminated, indicate a trouble condition.  A system trouble condition will 
also occur on the SP40S. 
 
 

LED trouble indication on the system when the SP4-RMX is connected to it. 

 
 

The system TRB LED indicator and D44 AUX IN LED indicator on the SP40S will illuminate when the SP4-RMX has a trouble 
condition.  
 
 

LED trouble indications on the SP40S and SP4-RMX when the SPB indicates a trouble condition. 

 
The system TRB LED indicator and D2 AUDIO SHORT LED indicator on the SP40S will illuminate; D29 SYS TRB and D23 WIRE 
SHT on the SP4-RMX when the SPB has a trouble condition. 

 
 

Use the following troubleshooting table to locate the trouble area. 

 
 

Table 4: 

Trouble LED Indicators 

 

D30 SYS 
PWR 

D29 SYS 
TRB 

LED 
Indicator 

Remarks 

ON OFF  

Normal 

OFF OFF  

24VDC not applied. Check PWR IN terminals. If 24VDC is present then SP4-RMS 
module is defective. Replace. 

ON ON 

 

RM CC input shorted in excess of 2 1/2 minutes or Defective SP4-RMX module. 

D22 WIRE 
Open 

AUD OUT circuit open or 10K Ohm EOLR missing. 

D23 WIRE 
SHT 

AUD OUT circuit shorted. 

D24 AUX 
TRB 

AUX IN circuit open or 10K Ohm EOLR missing. 

D25 ALM 
TRB 

ALM TRB circuit open or 10K Ohm EOLR missing. 

D26 RM1 
TRB 

RM1 CC circuit open or RM1 module in trouble condition. 

D27 RM2 
TRB 

RM2 CC circuit open or RM2 module in trouble condition. 

D28 RM3 
TRB 

RM3 CC circuit open or RM3 module in trouble condition. 

 
 
Malfunctioning modules should be returned to the manufacturer for repair or replacement. 

Содержание 109919

Страница 1: ...optional Remote Microphones SPRM or SPRM GP to three The PCB assembly is mounted in an enclosure READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT NOTE All CAUTIONS and WARNINGS are identified by the symbol All warnings are printed in bold capital letters SP40S Panel 24VDC 24VDC Audio Out Audio Out Aux In Aux In SP4 RMX MIC 1 MIC 2 MIC 3 SP4 RMX MIC 1 MIC 2 MIC 3 Audio Out Audio Booster ...

Страница 2: ...CHNICAL SPECIFICATIONS Electrical Input Voltage 24 VDC Input Current 52mA max RM Page 62mA max Standby Auxiliary Audio Input 1Vrms Min Ground Fault 20k Ohms Relay Ratings K1 and K3 2A 30Vdc 1pF K2 K4 K5 and K6 1A 30Vdc 1pF Remote Microphone SPRM Mechanical Dimensions H x W x D 13 0 x 7 6 x 2 15 33cm x 19 4cm x 5 4cm Weight 3 8 pounds 1 7kg Enclosure 0 050 Steel Finish Black Mounting Indoor Surface...

Страница 3: ...fully unpack the SP4 RMX and make sure each item described on the packing slip is present and undamaged 3 Mount the SP4 RMX in the desired location as described in the Mounting section 4 Mount any additional wiring boxes or junction boxes needed to interconnect field wiring 5 Connect conduit fittings or bushings as needed using knockouts provided on the top and bottom of the SP4 RMX units see Figu...

Страница 4: ...f the shield must be connected at the Safepath panel or SP4 RMX enclosure Maximum Length 20 Feet Restrictions All wiring between SP40S or Audio Booster and SP4 RMX must be run in conduit and within the same room When used with the SPB 160 SPB 80 4 or SPB320 the RMX must be located in the same room Between each SPRM and SP4 RMX Cable Size 14 22 AWG Shielded The shield must be connected only at the ...

Страница 5: ...P84557 F Sheet 5 of 14 6 00 CONDUITKNOCKOUTS 2 PLACES BOTHENDS 11 00 MOUNTINGHOLES MOUNTINGHOLES GROUND TERMINALS Figure 2 SP4 RMX Mounting NOTE Drawing is not to scale ...

Страница 6: ... ALL CONNECTIONS BETWEEN SP40S AND RMX ARE SUPERVISED THESE CONNECTIONS MUST BE RUN IN NO MORE THAN 20 FT OF CONDUIT AND WITHIN THE SAME ROOM ALL CONNECTIONS BETWEEN RMX AND REMOTE MICS ARE SUPERVISED Figure 3 Wiring Diagram with up to 3 Remote Microphones to an SP40S NOTE If the SP4 RMX is configured for less than 3 Remote Microphones the DIP switch for the unused Remote Microphone port SW3 must ...

Страница 7: ...ed SP4 RMX Modules AUX IN CC NAC SP40S 24 VDC 10K EOLR 10K EOLR 10K EOLR 10K EOLR S3 S2 S3 SW2 RM3 VOL RM2 VOL RM1 VOL 1V 25V 70V AUX VOL R37 J1 S3 S2 S1 SW2 RM3 VOL RM2 VOL RM1 VOL 1V 25V 70V AUX VOL R37 J1 Figure 4 Two Ganged SP4 RMX Modules Set switches and jumpers on the SP40S as follows Set jumper J4 to 1V position Set SW6 to the contact closure CC position Remove jumper JP4 to enable supervi...

Страница 8: ... MORE THAN 20FT OF CONDUIT AND WITHIN THE SAME ROOM REFER TO FIGURE 3 FOR SPRM GP CONNEC TIONS ALL CONNEC TIONS ARE SUPERVIS ED SP40S SP4 RMX SPB 10K OHM EOLR 10K OHM EOLR AUD OUT 24V OUT SPB SUP ALM NC NO C NC NO C TB4 TB1 TB6 24V OUT 24V OUT EXP OUT TB7 Figure 5 SP4 RMX Connections Diagram When Using an SPB ...

Страница 9: ...SPRM connected Insure the corresponding switch is OFF for any SPRM inputs not used Set switch S1 on SW2 to the desired position according to Table 1 Set S2 to ON Switch S3 to the ON position Set switches and jumpers on the SPB as follows Set SW3 to the CC contact closure position Remove jumper JP8 to enable supervision of the CC input wiring Move jumper J4 to the 1V position FIELD WIRING CHECKOUT ...

Страница 10: ...es of the SP40S and SPB audio boosters In SP40 mode each SP4 RMX provides the capability of connecting and supervising up to three SPRM emergency remote microphone modules In SPB mode the SPRM GP General Page Remote Microphones must be used These microphones are for general pages only These pages are non emergency messages Any trouble condition on the SPRM modules input and output wiring will ligh...

Страница 11: ...he SPB audio booster modules the SP40S AUDIO OUT is connected to the SP4 RMX AUX IN and the SP4 RMX AUDIO OUT is connected to the SPB AUDIO IN This means that the priority level of the SPRM GP modules are after the digital voice messages on the SP40S and are considered non alarm conditions Priority Levels on SPB with SP4 RMX Connected Table 3 Priority Levels SP4 RMX to SPB Priority Source Remarks ...

Страница 12: ...tion Use the following troubleshooting table to locate the trouble area Table 4 Trouble LED Indicators D30 SYS PWR D29 SYS TRB LED Indicator Remarks ON OFF Normal OFF OFF 24VDC not applied Check PWR IN terminals If 24VDC is present then SP4 RMS module is defective Replace ON ON RM CC input shorted in excess of 2 1 2 minutes or Defective SP4 RMX module D22 WIRE Open AUD OUT circuit open or 10K Ohm ...

Страница 13: ... 13 of 14 S3 S2 S1 SW2 RM3 VOL RM2 VOL RM1 VOL 1V 25V 70V AUX VOL R37 J1 AUX TRB ALM TRB RM1 TRB WIRE SHT WIRE OPEN SYS TRB SYS PWR D24 D25 D26 D27 D28 D23 D22 D29 D30 RM2 TRB RM3 TRB Figure 6 SP4 RMX PC Board Layout ...

Страница 14: ...ITABLE FOR THE USER S PURPOSES OR WHETHER IT WILL ACHIEVE THE USER S INTENDED RESULTS THERE IS NO WARRANTY AGAINST DAMAGE RESULTING FROM MISAPPLIACATION IMPROPER SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND SELLER S CONTROL SELLER DOES NOT WARRANT THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORM...

Отзывы: