5
Installation Instructions for the AUX Universal Edge Lit Exit
Usage Instructions for the Atlite Eagle Eye Self Diagnostics
The AtLite Eagle Eye Self Diagnostics is continuously monitoring your emergency fixture, and will signal any failure
through the 3 color indicator LED.
Initial Operation:
When the unit is first powered up, it will go into a 24 hour fast charge, indicated by the indicator LED pulsing green.
Once the unit has fully charged, it will perform a self calibration, after which the LED will change to steady green,
indicating the unit is fully charged and float charging the battery to maintain readiness.
Automatic Testing:
The unit will perform a battery capacity, lamp/LED, and charge circuit test every 30 days for 30 seconds. During this
time, the indicator LED will change to a steady yellow. It will perform a full battery capacity (90 minute) test once per
year. During this time, the indicator LED will change to a blinking yellow.
Manual Testing
• 10 Second “Installation” test – Press and release the test button once during fast charge (blinking green) to initiate a
10 second quick test. The sign will switch to emergency mode for 10 seconds allowing the installer to verify proper
installation of the unit, and the LED indicator will turn solid yellow.
• 30 Second Test - Press and release the test button once during float charge (steady green). The indicator LED will
turn steady yellow to indicate the unit is performing a 30 second test of the batteries and lamps/LEDs.
• 90 Minute Test - Press and release the test button a second time during a 30 second test (steady yellow) to change
to a 90 minute test. During this test, the LED indicator will change to blinking yellow, and the circuit will perform a
full battery capacity, charge circuit, and LED test.
• Canceling Test – Press and release the test button during the 90 minute test (flashing yellow) to return the fixture to
its original state (fast charge or float charge)
Clearing Failure Codes
• A battery failure (LED two blink red) can be cleared by replacing the battery. Disconnecting the battery and AC
power, or performing a full 90 minute discharge, will reset the error code, however, it will return if the battery is
faulty.
• Charge Circuit (LED three blink red) and lamp/LED failure will clear when the unit successfully passes a manual or
automatic 30 second test.
Indicators:
• LED Off - No power to unit, emergency mode.
• LED Steady Green - Unit is fully charged and is float charging the battery to maintain readiness.
• LED Green Pulse - Unit is in a 24 hour fast charge of the battery.
• LED Two Blink Red - Battery has failed a capacity test, or the battery is disconnected. See “Clearing Failure Codes”
above.
• LED Three Blink Red - Battery charge circuit has failed. See “Clearing Failure Codes” above.
• LED Four Blink Red - Lamps have burned out, or on an EXIT/Combo, 50% or more of the LEDs have failed. See
“Clearing Failure Codes” above.
• LED Steady Yellow - 30 second test or 10 second quick test (Fast Charge only).
• LED Blinking Yellow - 90 minute test.
LED FAILURE
QUICK TEST
OFF - EMERGENCY
MODE / POWER OFF
2 BLINK RED -
BATTERY FAILURE
STEADY GREEN -
FULL / FLOAT
CHARGE
STEADY BLINK YELLOW
- 90 MINUTE TEST
3 BLINK RED - CHARGE
CIRCUIT FAILURE
4 BLINK RED - LAMP/
STEADY YELLOW -
STEADY BLINK
GREEN - FAST
CHARGE
Atlite