![Cooper Crouse-Hinds CEAG GHG 619 Скачать руководство пользователя страница 22](http://html.mh-extra.com/html/cooper-crouse-hinds/ceag-ghg-619/ceag-ghg-619_operating-instructions-manual_2661974022.webp)
Cooper Crouse-Hinds GmbH
22
22
22
22
22
1.9
40A installation contactor
EC-Type Examination Certificate:
PTB 98 ATEX 1087U
Explosion protection:
Ex de II C
Temperature range:
for use in temperature classes T4-T6
Rated voltage:
up to 400V AC
Control voltage:
24V to 400V AC
Rated current:
Main contacts
NO - up to 40A
NC - up to 32A
Aux. contacts
up to 6A
Rated switching capacity - main contacts:
AC1 - 3-phase:
230V / 15.2kW
400V / 26kW
AC3 - 3-phase:
230V / 5.5kW
400V / 11kW
DC 3
1 current path
60V / 5A
220V / 0.3A
DC 3
2 current paths
60V / 16A
220V / 1.1A
DC 3
3 current paths
60V / 34A
220V / 4.5A
Rated switching capacity - aux. contacts:
AC 15
230V / 4A
400V / 3A
Back-up fuse:
63A gL
Terminal cross section:
Switching contacts 1, 2, 3, 4, 5, 6,
max. 2x 10mm²
/ 3.0 Nm
Control contacts A1, A2
max. 2x 2.5mm²
/ 1.5 Nm
Aux. contacts 7(13), 8(14) /optional ly21,22,33,34 max. 2x 2.5mm²
/ 1.5 Nm
Component size:
4
Weight:
ca. 1.65kg
Contact arrangement:
Main contacts
Aux. contacts
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
4NO 1NO+1NC 2NO
Explosion-protecded distributions GHG 619
Contact arrangements
Circuity
Ex41 - GHG 411 switches
Code
6060
6062
6065
. 061
. 063
. 067
Switch mechanism
4
5
6
Special
switch mechanism
7
8
9
Contact arrangements
Ex41 - GHG 411 Pushbutton
Mushroom-head pushbutton with interlock
2 Ö
2 S
1S+1Ö
Mushroom-head pushbutton with key release
2 Ö
2 S
1S+1Ö
Key-operated pushbutton
2 Ö
2 S
1S+1Ö
Pushbutton
2 Ö
2 S
1S+1Ö
Double pushbutton
2 Ö
2 S
1S+1Ö