Explosion-protecded distributions GHG 619
Component size 1
Dimension drawings for Ex-d components
Dimensions in mm
1.4
ELCB (RCD), 2 and 4-pole
EC-Type Examination Certificate:
PTB 98 ATEX 1087U
Explosion protection:
Ex de II C
Temperature range:
for use in temperature classes T4-T6
Rated voltage:
Main contact
Aux. contact
up to 440V AC
up to 250V AC
Rated current:
Main contakt
Aux.contakt
up to 63A
max. 5A
Short-circuit protection:
10 kA
Back-up fuse:
max. 100 A gL
Tripping current:
30mA (300mA on request)
Terminal cross section:
Main contact
Aux.contact
max. 2x 10mm²
max. 2x 2.5mm²
Test torques:
3.5 Nm
1.5 Nm
Component size:
2
4
Weight:
ca. 0.94kg
ca. 1.56kg
2-pole *
4-pole
Contact arrangement:
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
* ELCB's with signal contacts are built into component enclosures in the next size.
1.5
Circuit breaker, 1-pole+N, with ELCB (RCD)
EC-Type Examination Certificate:
PTB 98 ATEX 1087U
Explosion protection:
Ex de II C
Temperature range:
for use in temperature classes T4-T6
Rated voltage:
Main contact
Aux. contact
up to 440V AC
up to 250V AC
Rated current:
ELCB
up to 63A
Circuit breaker
from 1.0A up to 32A (40A)
Aux. contact
max. 5A
Short-circuit protection:
10 kA
Back-up fuse:
ELCB
max. 100 A gL
Circuit breaker
dep. on rated current up to 100A
Tripping current ELCB:
30mA (300mA on request)
Terminal cross section:
Main contact
Aux./Signal contact
max. 2x 10mm²
max. 2x 2.5mm²
Test torques:
3.5 Nm
1.5 Nm
Component size:
2*
3*
Weight:
ca. 0.95kg
ca. 1.27kg
Contact arrangement:
1-pole + N
2-pole
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
* ELCB with circuit breakers and signal contacts are built into component enclosures in the next size.
X = Fixing dimensions
Component size 2
Component size 3
Component size 4
Component size 0
Contact arrangement
Aux. contact Signal contact