Explosion-protecded distributions GHG 619
1.7
20A installation contactor
EC-Type Examination Certificate:
PTB 98 ATEX 1087U
Explosion protection:
Ex de II C
Temperature range:
for use in temperature classes T4-T6
Rated voltage:
up to 250V AC
Control voltage:
24V to 250V AC
Rated current:
20A
Rated switching capacity:
AC 1 230V / 4,0kW AC 3 230V / 1,3kW
Back-up fuse:
20A gL
Terminal cross section:
Switching contacs 1, 2, 3, 4
max. 2x 10mm²
/ 3.0 Nm
Control contacs A1, A2
max. 2x 2.5mm²
/ 1.5 Nm
Component size:
0
Weight:
ca. 0.55kg
Contact arrangement:
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
1NO+1NC
2 NO
2 NC
1.8
24A installation contactor
EC-Type Examination Certificate:
PTB 98 ATEX 1087U
Explosion protection:
Ex de II C
Temperature range:
for use in temperature classes T4-T6
Rated voltage:
up to 400V AC
Control voltage:
24V to 400V AC
Rated current:
Main contacts
up to 24A
Aux. contacts
up to 6A
Rated switching capacity – main contacts:
AC1 - 3-phase:
230V / 9.0kW
400V / 16 kW
AC3 - 3-phase:
230V / 2.2kW
400V / 4.0kW
DC 3
1 current path
60V / 4A
220V / 0.2A
DC 3
2 current paths
60V / 14A
220V / 1.0A
DC 3
3 current paths
60V / 24A
220V / 4.0A
Rated switching capacity – aux. contacts:
AC 15 230V / 4A
400V / 3A
Back-up fuse:
35A gL
Terminal cross section:
Switching contacts 1, 2, 3, 4, 5, 6,
max. 2x 10mm²
/ 3.5 Nm
Control contacts A1, A2
max. 2x 2.5mm²
/ 1.5 Nm
Aux. contacts 7(13), 8(14) /optional ly21,22,33,34 max. 2x 2.5mm²
/ 1.5 Nm
Component size:
3
Weight:
ca. 1.20kg
Contact arrangement:
Main contacts
Aux. contacts
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
4 NO
1NO+1NC 2 NC
Contakt arrangements
Circuitry
Ex 23 / Ex28 / Ex 29 switch
Code
6011
6019
6060
6062
6065
6033
6170
. 021
. 023
. 024
. 061
. 063
. 066
. 067
. 049
. 037
. 191
Switch mechanism
4
5
6
Special
switch mechanism
7
8
9
1.6
Current surge switch
EC-Type Examination Certificate:
PTB 98 ATEX 1087U
Explosion protection:
Ex de II C
Temperature range:
for use in temperature classes T4-T6
Rated voltage:
up to 400V AC
Rated operating voltage:
8V to 400V AC
8V to 220V DC
Rated current:
16A
Rated switching capacity:
16A / 250V AC
10A / 400V AC
Terminal cross section:
Switching contacts 1, 2, 3, 4
max. 2x 10mm²
/ 3.0 Nm
Control contacts A1, A2
max. 2x 2.5mm²
/ 1.5 Nm
Komponent size:
0
Weight:
ca. 0.55kg
Contact arrangement:
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.