Walk-Through  feature  maximizes  energy  savings  by  not  leaving  the  lights  ON  after  a  momentary  occupancy.    The 

sensor will switch the lights ON when it detects a person entering the area.  If the sensor does not continue to detect

motion 20 seconds following the initial activation, it will automatically go to a shorter 2 minute Time Delay.  

Installation Instructions

Model # ONW-D-1001-MV-N-W
Model # ONW-D-1001-MV-N-V
Model # ONW-D-1001-MV-N-LA
Model # ONW-D-1001-MV-N-G
Model # ONW-D-1001-MV-N-B

NeoSwitch Dual Technology Single Relay

Occupancy Sensing Wall Switch

(Neutral Required)

• Read all instructions on both sides of this sheet first.
• Install in accordance with ALL local codes.

• For indoor use only.

General Information

Cooper Controls
203 Cooper Circle, Peachtree City, GA 30269
800-553-3879
www.coopercontrol.com 

Technology:

Passive Infrared (PIR) and 

Ultrasonic (US)

Electrical Ratings 

120 VAC:

• Incandescent/Tungsten  –  Max.  load:  6.7  amps,

800W, 50/60 Hz

• Fluorescent/Ballast  –  Max.  load:  10  amps,  1200W,

50/60 Hz

Motor Load: ¼ HP @ 125 VAC
230/277 VAC:

• Fluorescent/Ballast  –  Max.  load:  9.8  amps,

2700W, 50/60 Hz

Ballast  Compatibility:

Compatible  with  magnetic  and

electronic ballasts

No Minimum Load Requirement
Time  Delays:

Self-Adjusting,  15  seconds/test  (10  min

Auto), Selectable 5, 15, 30 minutes

Coverage:

Major motion – 1000 sq. ft.
Minor motion –  300 sq. ft.

Light Level Sensing:

0 to 200 foot-candles

Operating Environment:

• Temperature: 32° F – 104° F (0° C – 40° C)
• Relative Humidity: 20% to 90% Non-condensing

Housing:

Durable,  injection  molded  housing.

Polycarbonate resin complies with UL94VO.

Size:

• Mounting Plate/Strap Dimensions:

4.195" H x 1.732" W (106.553 mm x 44 mm)

• Product  Housing  Dimensions:  2.618"  H  x  1.752"

W x 1.9" D (66.5 mm x 44.5 mm x 48.26 mm)

LED Indicators:

Red LED indicates PIR detection; Green

LED  indicates  Ultrasonic  detection;  Green  LED  acts  as
EcoMeter or night light locator.

Specifications

Description

Coverage

The  ONW-D-1001-MV-N  Occupancy  Sensing  Wall  Switch  is  a  Passive  Infrared  (PIR)  and  Ultrasonic  (US)  motion

sensing lighting control and conventional Wall Switch all-in-one, used for energy savings and convenience.

The sensor combines PIR and US technologies to monitor a room for occupancy. 

PIR Technology

The sensor’s segmented lens divides the field of view into sensor zones, and detects the changes in temperature

that are created when a person, or part of a person as small as a hand, passes into or out of a sensor zone.  

US Technology

The sensor produces a low intensity, inaudible sound.  It detects occupancy from changes in the acoustic waves

caused by motion, such as reaching for a telephone, turning a page in a book, walking into a room, turning in a swiv-

el chair, etc.  The sensor does not respond to audible sound. 

Dual Technology sensors ensure the greatest sensitivity and coverage for tough applications thus saving additional

energy.  PIR is used to turn the lights ON and then either or both technologies are used to keep the lights ON.

The ONW-D-1001-MV-N allows the control of one load with one occupancy sensor switch.  

The sensor can be configured to enhance energy savings by setting the unit for manual ON operation.

In Automatic ON Mode, the lights turn ON automatically when a person enters the room.  In Manual ON Mode, the

lights are turned ON by pressing the universally recognized light icon Pushbutton.  In either mode, the lights stay ON

as long as the sensor detects motion in the room.  When the room is vacated, the lights turn OFF automatically after

a preset Time Delay interval.

The  sensor  includes  self-adaptive  technology  that  continually  adjusts  to  conditions  by  adjusting  sensitivity  and

Time Delay in Real-time.  By adjusting sensitivity and Time Delay automatically, the sensor is maximizing the poten-

tial energy savings that are available in the particular application.

The EcoMeter provides a visual indicator of energy usage, increasing end user awareness and reminding individu-

als to take control of their lighting to maximize energy savings.

The Daylighting feature prevents lights from turning ON, when the room is adequately illuminated by natural light.

The ONW-D-1001-MV-N is designed for offices up to 300 square feet.  Coverage testing has been performed accord-

ing to the NEMA WD7 Guideline.

Location

When installing the ONW-D-1001-MV-N in a new junction box, choose the switch location carefully to provide opti-

mum coverage of the occupied area.  When replacing an existing Wall Switch, bear in mind that there must be a clear

Line-of-sight between the sensor and the area to be covered.  Avoid pointing the ONW-D-1001-MV-N directly into the

hallway where it may detect passers-by.

EcoMeter Operation

Load 1

EcoMeter LED

OFF

ON

ON

OFF

Action   

EcoMeter

Benefit

A person enters the space and

one of the loads is activated

OFF

The area is vacated and the

lights turn OFF automatically

ON

Increased awareness of energy savings; 

Acts as a night light locator

A person turns the lights OFF

manually upon exiting an area

ON

Increased awareness of energy savings and

reminds individuals to take control of their  

lighting for additional savings; Acts as 

a night light locator.

The daylighting feature prevents 

the lights from automatically

turning ON when a person 

enters an area

ON

Increased awareness of energy savings and

lets the individual know that the 

daylighting feature is working

Wiring

CAUTION:  Before installing or performing any service on a Greengate system, the power MUST be turned OFF
at the branch circuit breaker.  According to NEC 240-83(d), if the branch circuit breaker is used as the main
switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.”  All installations should
be in compliance with the National Electric Code and all state and local codes.

NOTE  REGARDING  COMPACT  FLUORESCENT  LAMPS:    The  life  of  some  compact  fluorescent  lamps  (CFLs)  is

shortened by frequent automatic or manual switching.  Check with CFL and ballast manufacturer to determine the
effects of cycling.

1. Make sure power is turned OFF at the branch circuit breaker.
2. Wire units as shown in wiring diagrams per applicable voltage requirements. 
3. Mount unit to Wall Box.
4. Turn power back ON at the branch circuit breaker and wait 2 minutes for the unit to stabilize.
5. Make necessary adjustments. (See Checkout and Adjustments section)
6. Install Wall Switch plate.

LOAD

120 to 277 VAC

BLACK

BLUE

NEUTRAL

GROUND

GREEN

WHITE

Wiring Diagram 1:

120 to 277 VAC single level 
single circuit wiring diagram

Installation

The  ONW-D-1001-MV-N  can  be  installed  in  any  standard  single

gang box.  It may be installed in the same manner as an ordinary Wall
Switch.

• Wire the ONW-D-1001-MV-N as described in the wiring section.
• Mount the ONW-D-1001-MV-N in the junction box.

,

36

8

,

Minor Motion, IR

Major Motion, IR

20

,

Maximum coverage area may

vary somewhat according to room

shape and the presence of obstacles.

The NEMA WD 7 Guide and robotic

method were utilized to verify

coverage patterns.

Minor Motion, Ultrasonic

Major Motion, Ultrasonic

,

10

8

,

,

15

20

,