Service diagnosis
3
4
Domestic air conditioner
10.3.5 IPM protection
Outdoor display: LED1 flash 2 times
Method of IPM protection is detected by checking the compressor running condition and so on
Malfunction
Detection
Malfunction The system leads to IPM protection due to over current
Decision The compressor faulty leads to IPM protection
Conditions circuit component of IPM is broken and led to IPM protection
Supposed IPM protection dues to the compressor faulty
Causes IPM protection dues to faulty PCB of IPM module
Compressor wiring disconnected
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Electrify the machine again and turn it on
with the remote controller,If malfunctions
are reported before or upon the compressor
being started up,
IPM Module is damaged and
needs replacing.
1
The system may have been over or under charged with gas, which can be judged through the pressure of the
measuring system.
2
The shaft of compressor is seized and the compressor needs replacing.
The compressor is started normally, but
malfunctions are reported after it has run for some
time.
Malfunction unsolved
Содержание TERRA CH-S09FHCP
Страница 12: ...Piping diagrams Domestic air conditioner 5 Piping diagrams 10 ...
Страница 14: ...Printed circuit board connector wiring diagram 12 Domestic air conditioner PCB ...
Страница 28: ...Seivice diagnosis Domestic air conditioner 8 Dimensional drawings unit mm 9 Center of gravity unit mm 26 ...
Страница 49: ... ...
Страница 50: ... ...
Страница 51: ... ...
Страница 52: ... ...
Страница 53: ... ...
Страница 54: ... ...
Страница 55: ... ...
Страница 56: ... ...
Страница 57: ... ...