background image

1)

Install the indoor unit temporarily

Attach the hanger bracket to the suspension bolt. Be sure to
fix it securely by using a nut and washer 

on

 the upper and

lower sides of the hanger bracket

, as shown in the figure

below.

1         Nut (field supply)
2         Washer (field supply)
3         Hanger bracket
4         Double nuts (field supply,

 

tighten)

1.3    Install the indoor unit

When installing optional accessories, read the installation 
manual 

for

 optional accessories. Depending on field conditions, it 

may be easier to install optional accessories before 

installing 

the 

indoor unit (except for the decoration panel).

 

However, for 

an 

existing ceiling, install 

the 

fresh air inlet component kit

 

and 

branch duct before installing the unit.

2)

Fix the paper pattern for installation (

f

or new ceilings only)

- The paper pattern for installation corresponds with the

measurements of the ceiling opening. Consult the builder for
details.

- The cent

e

r of the ceiling opening is indicated on the paper

 

pattern

for installation.

- After removing the packaging material from the paper patten for

installation, attach 

i

t to the unit

 

with the attached screws

,

 as

shown in 

the 

figure below.

3) Adjust the unit to the right position for installation

Refer to "Preparations before installation" on page 5.

1      Paper pattern for installation

 

(on some models)

 

2      Center of the ceiling opening
3      Screws

 

(supplied with the decoration panel)

1

2

3

4

1

2

3

4)

Check if the unit is horizontally level

- Do not install the unit tilted. The indoor unit is equipped with a

built-in drain pump and float switch. (If the unit is tilted against
the direction of the condensate flow (the drain piping side is
raised), the float switch may malfunction and cause water to

 

drip.

-

With a water level or water-filled vinyl tube, c

heck if the unit is

level at all four corners

,

 as shown in 

the 

figure below.

1         Water level
2         Vinyl tube

5) Remove the paper pattern for installation (

f

or new ceiling

only)

1

1

2

2

6

Содержание SOPHIA CH-09MSPHCT-230VI

Страница 1: ...nditioning unit Make sure to save this manual for future reference This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoo...

Страница 2: ...n oxygen deficiency Use the attached accessories parts and specified parts for installation Otherwise the set may fall or water leakage electrical shock or fire may result Install the unit in a strong...

Страница 3: ...ate the noise The appliance is not intended for use by young children or infirm persons without supervision Do not install the air conditioner in the following circumstances or locations The appliance...

Страница 4: ...rect The unit may malfunction or components may burn out Is the unit safely grounded Dangerous at electric leakage Is the wiring size according to specifications The unit may malfunction or components...

Страница 5: ...e properly drained The false ceiling is not on a noticeable incline There is sufficient clearance for maintenance and service There is no risk of flammable gas leaking The atmosphere is not potentiall...

Страница 6: ...installation contact your dealer NOTE 5 Installation is possible with a ceiling dimension of 600 mm 23 6 in marked with However to achieve a ceiling panel overlapping dimension of 15 mm 0 6 in the spa...

Страница 7: ...ing Consult the builder for details The center of the ceiling opening is indicated on the paper pattern for installation After removing the packaging material from the paper patten for installation at...

Страница 8: ...adio wave conditions 8 In coastal areas or other places with a salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not...

Страница 9: ...the wall height on the outlet side should be 1200 mm 47 2 in or less 1 Installing the outdoor unit 2 Drain work If drain work is necessary follow the procedures below Use a drain plug for drainage If...

Страница 10: ...0 2 0 Flare dimension A mm Flare shape O 6 35 1 4 in O 6 35 1 4 in 15 16 N m 153 163 kgf cm 8 3 8 7 0 327 0 343 in 12 0 12 4 0 472 0 488 in 15 4 15 8 0 606 0 622 in 18 6 19 0 0 732 0 748 in 25 26 N m...

Страница 11: ...ghtening torque 1 Connect the projection side of the charging hose which comes from the gauge manifold to the gas stop valve s service port 2 3 4 Fully open the gauge manifold s low pressure valve Lo...

Страница 12: ...utdoor unit is factory charged with refrigerant Calculate the added refrigerant necessary according to the diameter and length of the liquid pipe of the outdoor indoor unit connection 3 6 Refrigerant...

Страница 13: ...ain socket does not have to withstand unnecessary force To ensure a downward slope of 1 100 install hanging bars every 1 m 3 3 ft to 1 5 m 4 9 ft When unifying multiple drain pipes install the pipes a...

Страница 14: ...ration will restart automatically if the main power supply is turned off and then turned back on again Be sure to ground the air conditioner Do not connect the ground wire to gas pipes water pipes lig...

Страница 15: ...r supply terminal Looseness in the connection may cause overheating When connecting wires of the same gauge connect them according to the following figure 1 When attaching the control box lid make sur...

Страница 16: ...Grille hook Open the intake grille and remove 1 Decoration panel 2 Screws M5 supplied with the panel After installing the decoration panel ensure that there is no space between the unit body and the...

Страница 17: ...utton Check the following points If there is any malfunction please resolve it according to the Troubleshooting chapter in the user s manual The indoor unit The switch on the remote control works well...

Страница 18: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details...

Отзывы: