2)
Where applicable, create
the ceiling opening
that is
ne
cessary
for installation (
f
or existing ceilings)
- From the
side of the opening to the casing outlet, implement the
refrigerant and drain piping and wiring for
the
remote control
(unnecessary for
the
wireless type). Refer to each piping or
wiring
section.
- After making an opening in the ceiling,
you may need
to
reinforce
the
ceiling beams to
maintain
the ceiling level and to
prevent
it
from vibrating. Consult the builder for details.
3)
Install the installation hooks (
u
se either a
n
M8 or M10
bolt)
Use expansible hooks, sunken anchors
,
or other field
-
supplied
parts to reinforce the ceiling
so that it can
bear the weight of the
unit. Adjust
the
clearance from the ceiling before proceeding.
For
an i
nstallation example
,
see
the
figure below.
1 Ceiling slab
2 Expansible hook (optional)
3 Installation hook (optional)
4 False ceiling
For
details about
installation
other
than s
tandard
installation,
contact your dealer.
NOTE
5
Installation is possible with a ceiling dimension of 600 mm
(
23.6
in
)
(marked with * ). However,
to achieve a
ceiling-panel overlapping dimension of 15 mm
(
0.6
in
)
, the
spac
e
between the ceiling and the unit should be 20
mm
(
0.8
in
)
or less.
If the spac
e
between
the
ceiling and the
unit is
more than
20 mm
(
0.8
in
)
, attach sealing material
or recover the ceiling.
NOTE:
1 Indoor unit
2 False ceiling
1
2
24
mm
0.9
in
1
1
2
2
3
3
545/21.5
in
523/20.6
in
570/22.4
in
570/22.4
in
647/25.5
in
647/25.5
in
4
5
70/2.8
in
15/0.6
in
15/0.6
in
6
600/23.6
in
7
8
20/0.8
in
20/0.8
in
1 Installation hook
2
3
4
5
6
7
8
Indoor unit dimensions
D
ecoration panel dimensions
Refrigerant piping
Installation
hook (
x
4)
Ceiling opening dimensions
Hanger bracket
False ceiling
pitch dimensions
Adjust the position to ensure the gaps between the indoor
unit and the four sides of
the
false ceiling are even. The
indoor unit's lower part should sink into the false ceiling 24
mm
(
0.9
in
)
.
1.2 Preparations before installation
Relation of ceiling opening to unit and suspension bolt
position
1)
Unit: mm
30
-
35
mm
1.2
-
1.4
in
1
2
3
4