Circulating Air Source Heat Pump Water Heater

 

3.5 Installation of circulating water system   

(1)  Water  system  design  and  construction  must  be  complied  with  the  water-heating  design 

regulation and related standard requirement.   

(2) The unit adopts water flow switch as the cut-off protection, which is not equipped with the unit. 

Users should install it by themselves. Meanwhile, please ask project installer to adjust the cut-off point.   

(3) The pipe diameter for water outlet and water inlet of the unit should be decided by the rated flow 

volume  and  suggested  flow  speed  of  the  unit.  You  should  try  to  reduce  the  resistance  of  the  water 
system as much as possible.   

Below is the flow speed for the hot water pipe:   
Suggested value for the slow speed of the hot water pipe   

Diameter

mm

 

15

20 

25

40 

50 

Flow speed

m/s

 

0.8 

≤1.

≤1.

(4) When connecting the water pipe, please use PPR pipe to connect it to the water outlet and water 

inlet, and then connect it to the external water pipe.   

(5)  Water  pipe  and  valve:  For  ensuring  the  water  system  clean,  PPR  pipe  materials  should  be 

adopted. The common valves are cut-off valve, ball valve, check valve, shutoff valve, and so on. Copper 
core valve should be adopted. Adopt rubber belt for the thread airproof between valve and connection 
pipe to prevent polluting pipeline.   

(6) Water pipe should be installed horizontally and reasonably. Try to reduce elbows as much as 

possible for decreasing the resistance of water system.   

(7)  Water  pipe  must  be  thermal  insulated  to  prevent  heat  loss.  The  common  thermal  insulation 

materials are PEF, glass cotton, rubber insulation sponge, etc.   

(8) Thermometer and water pressure gauge should be installed at the water inlet pipe and water 

outlet pipe of unit for inspection during operation. You are suggest to adopt 0

100

  glass thermometer 

and 0

1.6MPa water pressure gauge. Install the strainer at the water inlet position of unit to prevent 

blockage of tubing heat exchanger and clean it periodically.   

(9) In general, the service valve should be installed in front of the electric solenoid valve on the 

system pipeline for future maintenance. For the convenient of cleaning system, blow down valve should 
be installed at the lowest position of the system.   

(10) The water makeup valve and cut-off valve for the system may need to be thermal insulated in 

winter to prevent breakage due to low temperature.   

(11) After the pipes for the water system is installed well, conduct water leakage and blowdown test 

according to related regulations to prevent damage to pipeline, tubing heat exchanger and water pump.     

(12) If the ambient temperature is very low in winter, no need to cut off the power after stopping 

operation. Otherwise, the freeze prevention protection may be invalid. If the unit won’t be used for a long 
time, please drain out the residual water inside the unit, the water tank and the pipeline through  the 
drainage valve.   

Содержание CH-HP20CMFNM

Страница 1: ... HP40CMFNM Thank you for choosing Air Source Heat Pump Water Heater please read this owner s manual carefully before operation and retain it for future reference Circulating Air Source Heat Pump Water Heater Owner s Manual Библиотека СОК ...

Страница 2: ......

Страница 3: ...ck whether the power is consist with that required on the nameplate and then check the safety of the power 2 Before operation please check and confirm whether electric wires and water pipes are connected correctly for preventing water leakage electric shock fire hazard and other accidents 3 The power socket must be equipped with earthing wire for ensuring reliable grounding for unit and preventing...

Страница 4: ...nment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use the return and collection systems or contact the retailer where the product was purchased They can take this product for environmental safe recycling When there re any problems please contact dealer appointed maintenance center o...

Страница 5: ... Before installation 6 3 2 Position before installation 6 3 3 Movement and installation of the unit 6 3 4 Installation space 7 3 5 Installation of circulating water system 8 3 6 Install the water flow switch 9 3 7 Construction and installation for the heating water tank 10 3 8 System installation diagram and instruction 11 4 Electric installation 16 5 DIP switch setting on main board 20 6 Debuggin...

Страница 6: ...stem Backwater pipe Condenser Evaporator Fan Air source energy input Electric energy input Electronic expansion valve Strainer Compressor Water supply pipe Water tank Inlet pipe of cold water Bushing condenser Exit pipe of hot water Gas liquid separator 1 3 Product features High efficiency and energy saving Adopt heat pump technology which can transfer the consumed electricity into three times of ...

Страница 7: ...odel Hot water mode Heating capacity kW 20 22 29 77 40 19 Heating Power Input kW 8 52 8 87 13 27 Heating Current Input A 13 9 16 9 26 Nominal Water Output L h 602 775 1140 Rated Input kW 10 1 13 2 19 Rated current Input A 20 24 38 Set temperature defaulted at 50 30 60 adjustable water tank temperature Power 380 415V 3N 50Hz Refrigerant Name R410A R410A R410A Refrigerant charge volume kg 4 2 4 2 5 ...

Страница 8: ...se is tested in the semi silencing room The actual noise will be a little higher in the actual operation environment Circulating water flow means the rated flow during the heating operation When selecting the water pump model it shall refer to the flow after overcoming the water resistance that is the flow of corresponding delivery lift rather than the maximum flow labeled in the nameplate of wate...

Страница 9: ... temperature Circulating water flow 6 2m 3 h Outdoor ambient temperature wet dry bulb 20 15 7 8 7 6 20 15 30 22 35 24 46 28 Heating Capacity kW 50 12 51 14 00 15 04 26 99 34 89 38 16 38 38 43 27 40 12 70 14 62 18 70 27 73 36 08 41 68 40 41 44 32 30 12 81 15 46 20 76 29 77 39 15 44 85 43 48 47 07 Heating Power Input kW 50 9 39 9 49 9 62 11 06 11 12 10 91 11 06 11 41 40 7 85 8 00 8 35 9 29 9 46 9 38...

Страница 10: ...Circulating Air Source Heat Pump Water Heater 5 2 4 Schematic plan for the unit outline Unit mm CH HP40CMFNM Unit mm CH HP20CMFNM CH HP30CMFNM ...

Страница 11: ...or any other places where s convenient for installation and bear the weight of the unit 2 The unit should be installed the well ventilated place and avoid the air discharge and noise disturb other people Please pay attention to the wind direction and avoid the strong wind 3 When placing the unit on the roof please pay attention to the wind direction to prevent strong wind 4 There should be no stro...

Страница 12: ...n the ground or roof Please confirm that the unit is placed horizontally See below fig 5 In case that the water heater is not under the lightning protection of the building then lightning protection measures should be taken according to the existing local national standards 3 4 Installation space 1 Single unit installation space for CH HP20CMFNM CH HP30CMFNM CH HP40CMFNM Unit mm 2 Modular unit ins...

Страница 13: ...tally and reasonably Try to reduce elbows as much as possible for decreasing the resistance of water system 7 Water pipe must be thermal insulated to prevent heat loss The common thermal insulation materials are PEF glass cotton rubber insulation sponge etc 8 Thermometer and water pressure gauge should be installed at the water inlet pipe and water outlet pipe of unit for inspection during operati...

Страница 14: ...that are 45mm 65mm 75mm or 85mm s long and 16mm s wide The paddle can be trimmed conditionally during installation Please make sure the rear part forms an arc that matches the pipe and the bottom of the paddle should be 10 20 above the pipe central line thus avoiding collision between the paddle and the inner surface of pipes as well as other objects inside water flow switch other valve fluid dire...

Страница 15: ...igher than the circulating water outlet to prevent water lacking during operation 2 The overflow port should be 50mm maximum higher than the water level switch to prevent overflow of water tank The overflow port must be connected with connection pipe and then lead it to the flow drainage outlet 3 The hot water inlet and the user back water outlet should point at the water level switch to prevent i...

Страница 16: ...diagram for signal unit system Fig1 Timer water supply installation diagram for single unit 2 Installation diagram for modular system Fig2 Timer water supply installation diagram for modular series Fig3 Non timer water supply installation diagram for modular unit the height of heating water tank is same as that of hot water storage tank ...

Страница 17: ...e low water level the water discharge solenoid valve water discharge pump between heating water tank and thermal storage water tank will be started up and then fill the thermal storage water tank with water If the water level switch of the thermal storage water tank is at the high water level the water discharge solenoid valve between heating water tank and thermal storage water tank water dischar...

Страница 18: ... the water temperature is increased to a certain temperature above set temperature backwater pump or backwater solenoid valve will be stopped for ensuring the water temperature requirement If user has requirement for water supply pressure Users are suggested to adopt water pump electric contact type pressure switch When the water pressure is lower than set value the water pump will be started up w...

Страница 19: ...tion diagram for the single unit system 2 Installation diagram for the modular system Instalaltion principle instruction 1 In order to prevent water freezing in the water side heater exchanger and pipeline add ethanol and propyl alcohol in water However prohibit adding salt into water for preventing corrosion and damage to the unit The water side heat exchanger inside the unit can t comply with th...

Страница 20: ...circulating water pump will make the water inside the swimming pool pass through removable plate type heat exchanger for the second time heat exchanger When the water temperature in the swimming pool reaches the set temperature the unit will stop operation Because swimming pool system is the second time heat exchanging there s temperature difference of heat exchanging at unit side and swimming poo...

Страница 21: ...struction manual by professional person Caution If the wiring is changed due to improvement of product please refer to the wiring diagram on the unit Caution For the consideration of safety the leakage protection device at the power side The detailed position is as shown in below fig Project electric cabinet Leakage protection device Leakage protection device Leakage protection device Leakage prot...

Страница 22: ...Circulating Air Source Heat Pump Water Heater 17 ...

Страница 23: ... can let the temperature wire support 100N tension force 2 Slave module 3 Connection among modules CN15 CN25 CN15 CN25 CN25 CN15 Wired controller 1 unit 2 unit 3 unit CN2 CN1 inspection board 4 Wiring layout If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard Disconnect the power supply before cleaning an...

Страница 24: ...n Stationary appliances not fitted with means for disconnection from the supply mains having a contact separation in all poles that provide full disconnection under overvoltage category III the instructions state that means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules Model Power type Min sectional area of power cord mm 2 Capacity of air switch A L...

Страница 25: ...g Water Remark 3 Refer to item 3 in 5 Safety Notices for Using Water 5 DIP switch setting on main board Note 1 This instruction is only applicable for the main board of water heater 2 Please ask professional person to operate the DIP 3 Cut off the power before operating the DIP There are two groups DIP for the main board of water heater The first SA3 4 bit DIP group is the address DIP for the unit...

Страница 26: ...s are 2 3 16 in turn Because all the units are the same you can appointed the most convenient unit in the product as the 1 unit and connect wires according to the wiring diagram of master unit in this instruction manual Address DIP of unit black part is the deflector rod DIP Position Address Instruction SA3 1 2 3 4 ON pull the deflector rod to the direction of ON the opposite direction is OFF ON O...

Страница 27: ... the control wiring are connected correctly and tightly whether the grounding is reliable and whether all wiring terminals are fixed tightly 6 2 Test run Note Test run must be conducted when all above checkup items are qualified and guided by professional persons 1 Energize the unit and then turn on the unit As for the unit adopting three phase power if the power cord is connected reversely the ph...

Страница 28: ...lean the strainer inside the water system periodically to prevent protection or damage to the unit due to blockage of the water system Meanwhile frequently check whether the water supplement device inside the water system is normal 5 If the ambient temperature in winter is below 0 prohibit cutting off the power When the unit won t be used for a long time you should not only discharge the water ins...

Страница 29: ...quence Check it and connect it tightly Check the malfunction causes and resolve it Set it again Replace compressor Big noise for fan The fixing bolt for the fan is loose Blades touch outer case or grille The fan can t operate placidly Tighten the fixing bolts of fan Check it and adjust it Replace the fan Big noise for the compressor There s liquid slugging when liquid refrigerant entering into com...

Страница 30: ...erature sensor Floor heating mode OFF Hot water mode Auto F9 Malfunction of water outlet temperature sensor Floor heating mode OFF Hot water mode Auto E1 High pressure protection OFF Auto E3 Low pressure protection OFF Auto E4 Discharge high temperature sensor protection OFF Auto E5 Overload protection for compressor OFF Auto E6 Communication malfunction OFF Auto E0 Overload protection of water pu...

Страница 31: ...wo times within 40mins the reset method should be switched to manual from auto type 4 If low overload protection for compressor or fan motor is detected for the three times within 30mins the reset method should be switched to manual from auto type If there s quality problem or the unit can t operate normally within the warranty period please contact local maintenance center for free repair User mu...

Страница 32: ......

Отзывы: