background image

Safety 

Precautions

 Page 9

 

and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % 
maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of 
detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and 
corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/ extinguished. 
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from 
the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. 
Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the 
brazing process.  

When breaking into the refrigerant circuit to make repairs or for any other purpose conventional 
procedures shall be used. However, it is important that best practice is followed since flammability is a 
consideration. The following procedure shall be adhered to:
Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert gas; Open the 
circuit by cutting or brazing.   

The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed 
with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or 
oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system 
with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and 
finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. 
When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable 
work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take 
place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is 
ventilation available.

 
 

10.Detection of flammable refrigerants

The following leak detection methods are deemed acceptable for systems containing flammable 
refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity 
may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a 
refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for 
the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant 

11.Leak detection methods

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or 
any other adverse environmental effects. The check shall also take into account the effects of aging or 
continual vibration from sources such as compressors or fans.

9.Cabling

12.Removal and evacuation

13.Charging procedures

In addition to conventional charging procedures, the following requirements shall be followed. Ensure
that contamination of different refrigerants does not occur when using charging equipment. Hoses or 
lines shall be as short as possible to minimise the amount of refrigerant contained in them. 
Cylinders shall be kept upright.
Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it 
shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior 
to commissioning. A follow up leak test shall be carried out prior to leaving the site.

Under no circumstances shall potential sources of ignition be used in the searching for or detection 
of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

 

Содержание CH-D014WDR20

Страница 1: ...14WDR20 CH D022WDR20 Thank you for choosing our product For proper operation please read and keep this manual carefully Designed by Cooper Hunter International Corporation Oregon USA www cooperandhunt...

Страница 2: ...tures 13 Removing the collected water 15 Other features 14 Clean the grille and case 17 Clean the bucket 17 Troubleshooting Tips 18 Clean the air filter 17 When not using the unit for long time period...

Страница 3: ...the unit Do not use the machine near flammable gas or combustibles such as gasoline benzene thinner etc Do not drink or use the water drained from the unit Do not take the water bucket out during oper...

Страница 4: ...n damaged contact a technician or customer service for assistance In a thunderstorm the power must be cut off to avoid damage to the machine due to lightning Do not run cord under carpeting Do not cov...

Страница 5: ...of such waste separately for special treatment is necessary It is prohibited to dispose of this appliance in domestic household waste For disposal there are several possibilities When using this dehu...

Страница 6: ...manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants The appl...

Страница 7: ...able material 4 Checking for presence of refrigerant The area shall be checked with an appropriate refrigerant detector prior to and during work to ensure the technician is aware of potentially flamma...

Страница 8: ...supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing t...

Страница 9: ...ions on the pipe work are to take place Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available 10 Detection of flammable refrigerants The fo...

Страница 10: ...g order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered r...

Страница 11: ...al performance of our products the design specifications of the unit are subject to change without prior notice Control panel Panel Water level window Water bucket Water bucket Handle both sides Handl...

Страница 12: ...ure damage The dehumidifier must be operated in an enclosed area to be most effective Close all doors windows and other outside openings to the room A dehumidifier operating in a basement will have li...

Страница 13: ...ing the filter press the Filter button and the light will go off Press the filter button for 3 seconds when the unit is on or off to initiate the Wireless connection mode The LED DISPLAY shows AP to i...

Страница 14: ...r not replaced in the Wait 3 minutes before resuming operation After the unit has stopped it can not be restart operation in the first 3 minutes This is to protect the unit Operation will automaticall...

Страница 15: ...aining until start The selected time will register in 5 seconds and the system will automatically revert back to display the previous humidity setting When the Auto Start Auto Stop times are set withi...

Страница 16: ...ale threaded end When you remove the plastic cover if there is some water in the back drain outlet of the unit you must dry it Make sure the hose is secure so there are no leaks and the end of the hos...

Страница 17: ...nd add a little mild detergent Swish it around in the bucket empty and rinse Note Do not use a dishwasher to clean the bucket After clean the bucket must be in place and securely seated for the dehumi...

Страница 18: ...tion may be loose Intend to use the bucket to collect water but the back drain plug is removed This is normal The dehumidifier has Auto defrost feature These are error codes and protection codes See t...

Страница 19: ......

Страница 20: ...ternational Corporation Oregon USA www cooperandhunter com E mail info cooperandhunter com Cooper Hunter is constantly working to improve their products so the information in this manual is subject to...

Страница 21: ...CH D014WDR20 CH D022WDR20 Cooper Hunter Designed by Cooper Hunter International Corporation Oregon USA www cooperandhunter com RU...

Страница 22: ...03 13 15 14 17 17 18 17 17 11 11 12 12 12...

Страница 23: ...Safety 3...

Страница 24: ...4 8 15 250...

Страница 25: ...5 R290 1 CO2 2 3...

Страница 26: ...6 R32 R290 4 R32 R290 2...

Страница 27: ...7 2 6 1 1 2 3 4 5 3 4 5 CO2 6 7...

Страница 28: ...8 8 1 2 9 7 8...

Страница 29: ...9 10 11 LFL 25 OFN 9 12 OFN OFN OFN 13...

Страница 30: ...10 15 16 14 80...

Страница 31: ...11...

Страница 32: ...24 5 C 41 F 32 C 90 F 30 RH 80 RH 20 40 5 C 41 F 5 C 41 F 12 1 1 1 20 40 20 20 40...

Страница 33: ...ull Defrost On Off Full Auto defrost On Off Full Defrost TIMER On Off Defrost Full CONT POWER PUMP COMFORT FILTER TURBO ION TIMER On Off Defrost Full CONT POWER DRYER COMFORT FILTER TURBO ION 13 FILTE...

Страница 34: ...35 85 5 0 24 POWER 0 COMFORT 14 Bucket Full Light 30 3 3 3 ION 35 85 0 24 5 30 90 AS ES P2 P2 Eb...

Страница 35: ...15 250 Auto Stop Auto Start Auto Start Auto Stop 0 5 10 1 24 5 On Off 0 0 P2 1 1 P2 1 2 3...

Страница 36: ...16 8 Eb 8 Eb 1 4 15 2 5 16 ID M1 3 3 5 1...

Страница 37: ...17 0 C 32 F 13 2 1...

Страница 38: ...18 5 C 41 F ES AS P2 Eb 1Hz...

Страница 39: ......

Страница 40: ...Designed by Cooper Hunter International Corporation Oregon USA www cooperandhunter com E mail info cooperandhunter com Cooper Hunter...

Отзывы: