ALSPA PROFIBUS Field Bus Coupler
3. Installation
(09/06)
Technical Manual
Page 3-5
The MVS3007-4002 board is supplied with a terminator PCB that
must be removed to gain access to switch S2. Replace the
terminator PCB after adjusting switch S2.
3.4.1 Switch
Settings
The MVS3007-4002 PROFIBUS board has one Dual-in-Line switch,
S2, which must be configured as per Table 3-3.
Table 3-3 Switch S2 meanings
S2.1 S2.2 S2.3 S2.4 Dual Port RAM
Address (Hex)
Menu Activated
On*
On* Off
Off
F000 – F3FF
Menu 75
Off
On
Off
Off
F400 – F7FF
Menu 74
*