DZR-45
8
LED indication humidification
switched on
LED indication dehumidification
switched on
Indication 0-10 Volt level
Readout window
On/Off switch
Pushbuttons
LED indication humidification
relay switched on
LED indication dehumidification
relay switched on
Relais connections
Relay
Function
1
Humidification
2
Dehumidification or humidification 2
3
Thermostat
4
Alarm
230V connection
Connect the incoming mains voltage to terminals L and N. When the main switch is set
to ‘On’, L will be connected through to L’.
It is then possible to connect, a humidifier to L’, for example.
Optimization of energy and water consumption.
A humidifier also uses energy (10 Watt) and water (rinse program) in the stand-by posi
-
tion (230V switched on, no humidity generation).
You can reduce this by switching off the humidification completely if the RH is 10%
higher than desired. The dehumidification relay is used for the connection. The
dehumidification bandwidth must thereby be set to 10%. Up to and including the HU-85,
the humidifier can be connected directly to the relay. If an HU-245 humidifier is
installed, an auxiliary relay must be used. See the connection diagram on page 20.
7. OPERATION
Figure 5. Operation.
IMPORTANT
- Ensure that all the connections are soldered when lengthening a cable.
- In order to prevent interference, ensure that low-voltage cables (0-10V) are
never installed parallel to high-voltage lines (230V).
- Sensor wiring must cross electricity lines at a 90˚ angle.