DZR-45
10
Hygrostat with max.
This hygrostat operates in the same manner as the single hygrostat, but with an
additional sensor for maximum humidification. The additional sensor can be
placed in an air channel in order to limit the maximum humidity.
The sensor can be selected as follows:
Hygrostat -> maximum humidification -> sensor selection.
This will limit the humidification as soon as the measured relative humidity has
reached the set maximum value.
The set maximum value can be adjusted as follows:
Hygrostat -> maximum humidity -> humidity set point.
The setting for the bandwidth can be found under:
Hygrostat -> maximum humidity -> bandwidth.
Figuur 8. Hygrostat with maximun control.
Double hygrostat
In principle, this is the same as 2 single hygrostats. The regulation of
dehumidification is hereby not possible.
The output of hygrostat 2 uses the dehumidification output.
Two hygrostat submenus are available in the main menu.
In this way, 2 areas can be monitored with one controller.
Block mode
In block mode, the regulator is divided into several blocks with settings. Each
block can be activated based on time and/or an external signal. This makes it
possible for the configuration to operate during the day with a variety of settings.
It is also possible to indicate a fluid type for each block. This feature allows the
regulator to supply R.O. water or another fluid to the humidifier.
For comprehensive information, please refer to chapter X Block configuration
HK-01
0-10 Volt
Ca. 500 cm
HS/91 in room (Sensor 1)
DZR-45
HS/91 in duct (Sensor 2)