CONTROL PANEL INPUTS AND OUTPUTS 

The panel has one analog input and up to one digital input available to monitor other components, 
senders or signals.  These inputs can be used for a number of purposes including alarms and shut 
downs.  

 

Input 

Heading 

Default 

Options 

Connector 

Pin 

Digital 1 

Normally 

Open 

Open / Closed  

 

 

Function 

None 

 

Message 

None 

 

Check 

Off 

Off / Always / Run 

Output 

Heading 

Default 

Options 

Connector 

Pin 

Relay 1 

Function 

Fuel/Run 

  

 

 

Polarity 

Positive 

 

Initial State  On 

 

  

  

  

Relay 2 

Function 

Pre Heat 

  

 

 

Polarity 

Positive 

 

Initial State  Off 

 

  

  

  

Relay 3 

Function 

None 

  

 

 

Polarity 

Positive 

 

Initial State  Off 

 

  

  

  

 

Digital Outputs 

1)

 

Alarm – Engine shutdown when active with display message as assigned.  A red lamp will also 
be illuminated. 

2)

 

Pre Alarm – Warning message will be displayed along with a yellow lamp when active. 

3)

 

Pre Alarm & Alarm - Energizes an external audible alarm when a pre alarm or alarm condition 
is present.  Pressing the ENTER button will silence. 

4)

 

Alarm Horn - Energizes an external audible alarm when an alarm condition is present.  
Pressing the ENTER button will silence. 

5)

 

Engine Run - Relay will be active when engine RPM is greater than 600.  Typically used to 
drive an auxiliary circuit such as louvers or send a signal to a monitoring station. 

 
6)

 

Low Oil Press Alarm - Relay closes if a low oil pressure shutdown is detected.  
 

7)

 

High Coolant Temp Alarm - Relay closes if a high engine temperature shutdown is detected.  
 

8)

 

Over Speed Alarm - Relay closes if an over speed shutdown is detected.  

 

Содержание MVP-903

Страница 1: ...r MVP 903 Revision 2 0 ______________________________________________________________________________________________________________________________________ Copyright Controls Inc P O Box 368 Sharon...

Страница 2: ...ATION 2 MODULE CONNECTOR 4 CONTROL PANEL SPECIFIC CONFIGURATION 5 ENGINE ALARMS CODES AND MESSAGES 5 ALARM ANNUNCIATION AND CODE READER PANEL INDICATION LAMPS CONTROL PANEL ANALOG AND DIGITAL INPUTS 7...

Страница 3: ...CONTROLS INCORPORATED C O N T R O L S Y S T E M S S O L U T I O N S 2 INSTALLATION INFORMATION...

Страница 4: ...O L S Y S T E M S S O L U T I O N S 3 MODULE CONNECTOR INFORMATION BATTERY CAN HIGH CAN LOW SPEED INPUT FUEL LEVEL INPUT BATTERY BATTERY DIGITAL INPUT 1 FUEL RUN TEMP INPUT OIL PRESS INPUT PREHEAT OU...

Страница 5: ...Fuel Pre Alarm 20 0 100 Low Fuel Alarm 1 0 100 Fuel Alarm Delay 0 05 0 01 1 40 Sec Oil Pressure Check Run Off Always Run Low Oil Press Pre Alarm 15 0 100 PSI Low Oil Press Alarm 10 0 100 PSI Oil Pres...

Страница 6: ...CONTROLS INCORPORATED C O N T R O L S Y S T E M S S O L U T I O N S 5 Indicator Lamps Engine Fault Lamp Engine Alarm Lamp...

Страница 7: ...Digital Outputs 1 Alarm Engine shutdown when active with display message as assigned A red lamp will also be illuminated 2 Pre Alarm Warning message will be displayed along with a yellow lamp when act...

Страница 8: ...m 1 Reserved for OEM applications 13 Preheat Relay will be active during programmed preheat period Used to drive a preheat relay Digital Function Activation 1 Off Always Run Describes when the paramet...

Страница 9: ...croll menu options Press UP arrow button to enter menu Press DOWN arrow button to reverse Exit Menu System Hold MENU button and press ENTER button To Change a Setting Press ENTER button to bring up br...

Страница 10: ...iew Control Unit Software Version View Controller Setup Quick Setup 1 PASSWORD PROTECTED Engine Parameter Configuration 2 Input Configuration 3 Output Configuration 4 Engine Safety Configuration 5 Mod...

Страница 11: ...Default Positive Digital B2 Initial State Default On Digital B5 Function Default Preheat Digital B5 Polarity Default Positive Digital B5 Initial State Default Off Digital B6 Function Default None Digi...

Страница 12: ...ature Alarm High Temperature Pre Alarm High Temperature Alarm Temperature Alarm Action Temperature Alarm Delay Battery Voltage Check Low Battery Pre Alarm High Battery Pre Alarm Over Speed Alarm Over...

Страница 13: ...oltage Transmit Default On Hours Transmit Default On Engine Status Transmit Default Off Panel Status Transmit Default Off Panel Information Transmit Default Off Fault Transmit Default All Engine ID Au...

Страница 14: ...elease Load Default 0 Clutch 1 Release Coolant Temperature Default 150 F Clutch 1 Release Delay Default 0 00 Clutch 1 Release Interval Default 0 00 Clutch 2 Engage Trip Default None Clutch 2 Engage Sp...

Отзывы: