CONTROLS, INCORPORATED
C O N T R O L S Y S T E M S & S O L U T I O N S
- 11 -
CONTROL PANEL DIGITAL INPUTS
The panel has three digital inputs with one available to monitor other components, senders or
signals. This input can be used for a number of purposes including alarms and shut downs.
Input
Heading
Default
Options
Connector
Pin
Digital A4
Normally
Open
Open / Closed
A
4
Action
None
See Note 1
Message
None
See Note 1
Check
Always
Off / Always / Run
Digital B2 Action
Throttle Up
None
B
2
Digital B5 Action
Throttle Down
None
B
5
Note 1:
Message options available for Digital A4:
Action options available for Digital A4:
1)
Alarm – Engine shutdown when active with display message as assigned. A red lamp will also
be illuminated.
2)
Pre Alarm – Warning message will be displayed along with a yellow lamp when active.
3)
Soft Alarm – Recoverable Alarm. Engine will shut down as soon as this input is tripped, but
will recover to running if the condition is cleared quickly enough.
4)
None – Set to “None” when no functionality is required.
1)
None
12)
Low Pump Oil
2) Custom
13) Low Fuel Level
3) Low Water
14)
Override Active
4) Low Oil
15)
Polish Filter
5)
Low Engine Oil
16)
Low Hydraulic Fluid
6)
Hi Temperature
17)
Vacuum High
7) Low Pressure
18)
High Hydraulic Temperature
8)
External Shutdown
19)
Inlet Pressure Loss
9)
E-Stop
20)
Pipe Pressure Alarm
10)
Remote E-Stop
21)
Low Coolant Level
11)
High Pump Temp
22)
Air Filter