background image

 

 

Available Generator Information 

Additional generator information is available via the 

Generator Parameters menu

 

Total Reactive Power 

 

Power Factor 

 

Total Apparent Power 

 

Power Factor Phase (Lead or Lag) 

 

Generated Power (Total kWH) 

 
 
Sleep Mode 

To minimize current draw, the panel goes into a sleep mode two minutes after being set in auto 
mode.  In sleep mode, the display goes blank and the red lamp blinks once every ten seconds.  The 
engine ECU is also turned off. 
Upon receiving a signal from the remote start input, the panel wakes up, the display turns back on 
and normal operation commences. 
Pushing any of the four buttons wakes up the panel and turns the display on.  It will return to sleep 
mode after a two minute period. 

 

                                         

Sleep Mode  

Red Lamp Blinks 

Every Ten Seconds 

 

Display is Blank 

Содержание G3-100-AS

Страница 1: ...100 AS Revision 1 0 ______________________________________________________________________________________________________________________________________ Copyright Controls Inc P O Box 368 Sharon Cen...

Страница 2: ...S 8 ENGINE ECU ALARMS DE RATE SHUT DOWNS PANEL ALARM ANNUNCIATION AND CODE READER PANEL INDICATION LAMPS ACTIVE AND STORED ENGINE ECU CODES CONTROL PANEL SPECIFIC ALARMS AND SHUT DOWNS 10 CONTROL PANE...

Страница 3: ...d for the preheat function in the Output Configuration menu typically relay 1 or 3 CAN Configuration menu Function Description Default Value Source Address Match panel and ECU source address for prope...

Страница 4: ...position 2 Engine Stop Turn key to off position Automatic Start Stop 1 Turn key to auto position 2 Close Remote Start input to ground to start engine 3 Open Remote Start input to stop engine Auto Sta...

Страница 5: ...ep mode two minutes after being set in auto mode In sleep mode the display goes blank and the red lamp blinks once every ten seconds The engine ECU is also turned off Upon receiving a signal from the...

Страница 6: ...8 J1939 Low 2 Relay 1 9 Relay 3 Common 3 Relay 3 10 Not Used 4 Relay 2 4 Common 11 Battery Positive 5 Relay 4 Crank Signal 12 Battery Negative 6 Relay 1 Common 13 Analog 1 Input 7 J1939 High 14 Remot...

Страница 7: ...6 PANEL CONNECTORS Suggested 21 Pin Engine Connector Pin Function B Battery Positive E Battery Negative G Key On Power D Crank Signal V J1939 High U J1939 Low M Mill Lamp Signal X Digital Input 1...

Страница 8: ...7 XCAN AC Connector DT04 4P Pin Function Pin Function 1 Battery 3 J1939 CAN Low 2 J1939 CAN High 4 Battery Mating Connector DT06 4S...

Страница 9: ...es or shuts down the engine when it is not operating within normal parameters This includes more common shut downs like high engine temperature and low oil pressure but can encompass a large range of...

Страница 10: ...the ability to check the engine ECU for all ACTIVE and STORED engine ECU codes These codes can be viewed via the Active Codes and Stored Codes menus In addition the control panel has its own Alarm Eve...

Страница 11: ...re Alarm 15 0 100 PSI Low Oil Press Alarm 10 0 100 PSI Oil Press Alarm Delay 5 0 01 1 40 Sec Temperature Check Run Off Always Run Low Temp Pre Alarm 0 0 300 Deg F Low Temp Alarm 0 0 300 Deg F High Tem...

Страница 12: ...ble Inputs not highlighted in bold need to be enabled in the Input Configuration menu to activate Analog Inputs Input Heading Default Connector Pin Analog 1 Function None 14 Pin 13 Digital Inputs Inpu...

Страница 13: ...module using a standard Stewart Warner scale sender of 10 ohms 180 ohms 10 0 PSI and 180 150 PSI Sender ground must be common with battery negative 6 Oil Pressure bar Oil pressure in bar can be measur...

Страница 14: ...or alarm conditions Run refers to when the engine is running Off disables the alarm conditions Always enables the alarm constantly regardless of engine state 2 Alarm Delay The time period after Sender...

Страница 15: ...ay Functions A total of four relays can be assigned for different uses depending on application a None Assign to none when not used b Start Warning Relay will be active during auto start delay period...

Страница 16: ...external audible alarm when an alarm condition is present Pressing the ENTER button will silence l Low Oil Press Alarm Relay closes if a low oil pressure shutdown is detected m Hi Coolant Temp Alarm...

Страница 17: ...button to enter menu Press DOWN arrow button to reverse Exit Menu System Hold MENU button and press ENTER button To Change a Setting Press ENTER button to bring up brackets Press UP arrow button and D...

Страница 18: ...vent Log View Last 32 ECU and Controller Alarms Engine Parameters View ECU Engine Information Load Torque Oil Temp etc Engine Identification Engine Model View Engine Serial View Module Information Con...

Страница 19: ...3 Selection Multistate Speed 4 Selection 4 Engine Safety Configuration Sender Check Bypass Time Period Selection Fuel Level Check On Off Selection Low Fuel Level Pre Alarm Selection Low Fuel Level Ala...

Страница 20: ...s Default 234 Engine Address Default 0 Oil Fuel Transmit Default Off 7 Auto Start Configuration Auto Start Delay Default 10 seconds Pre Heat Time Default 0 seconds Crank Time Default 10 seconds Crank...