19
(5)
Module Configuration
LCD Auto Contrast On/Off
LCD Contrast % (Default 55%)
LCD Backlight % (Default 100%)
Display Mode ((Default = Hours)
Voltage Display (Default = Line to Line)
Activation Frequency (Default 47.0 Hz)
Activation Delay M:S (Default 0:02)
Deactivation Frequency (Default 20.0 Hz)
KHW Reset Yes/No
Pressure and Temperature Units (Default = English)
Hour meter Source (Default = Engine ECU)
Hour meter Reading
Display Battery Source (Default = J1939)
Clear Operation Log
Clear Alarm Log
(6)
CAN Configuration
Source Address (Default = 44)
TSC1 Address (Default = 234)
Engine Address (Default =0)
Oil/Fuel Transmit (Default = Off)
(7)
Auto Start Configuration
Auto Start Delay (Default = 10 seconds)
Pre Heat Time (Default = 0 seconds)
Crank Time (Default = 10 seconds)
Crank Rest Time ( Default = 10 seconds)
Warm Up Speed (Default = 800 rpm)
Warm Up Time (Default = 0 seconds)
Operate Speed (Default = 800 rpm)
Cool Down Speed (Default = 800 rpm)
Cool Down Time (Default = 0 seconds)
Crank Cycles (Default = 5)
Fault Bypass Period (Default = 10 seconds)
Crank Hold Delay (Default = 0)
Crank Release Speed (Default = 400 RPM)
Recharge Monitor (Default = Off)
Recharge Voltage Selection
Recharge Delay Selection
Recharge Run Time Selection
Next Recharge Time Interval Selection
(8)
XCAN-AC Configuration
XCAN-AC Configuration
(DO NOT ACCESS – FOR CI USE ONLY)