CONTROL PANEL DIGITAL INPUT
The panel provides the analog and digital inputs defined below located in the
Input Configuration
menu
.
The panel is shipped from the factory with the
highlighted
inputs enabled in the panel.
Inputs
not highlighted need to be enabled/configured in the menu system to be used.
Input
Heading
Default
Options
Connector
Pin
Digital 1
Normally
Open
Open / Closed
16 Pin
Connector
B
Function
None
Message
None
Check
Always
Off / Always / Run
DIGITAL FUNCTIONS
The digital inputs can be configured for different uses depending on the application. These
include the following:
1)
Alarm – Engine shutdown when active with display message as assigned. A red lamp will also
be illuminated.
2)
Pre Alarm – Warning message will be displayed along with a yellow lamp when active.
DIGITAL FUNCTION MONITORING
Off / Always / Run – Describes when the parameter will be monitored for alarm conditions. Run refers
to when the engine is running. Off disables the alarm conditions. Always enables the alarm constantly
regardless of engine state.
DIGITAL FUNCTION DELAYS
Alarm Delay – The time period, after Sender Check Bypass, that the parameter must be on the alarm
condition before the alarm becomes latched.