LEDs 

behaviour

Error

Actuator use

Actuator behaviour

Typical 

trouble 

shooting 

condition

Reset 

procedure

Automatic calibration  

(DIP N. 7 OFF)

Manual calibration  

(DIP N. 7 ON)

1

RED ON

Valve stroke 

less than 

5mm

Calibration/first 

installation

The actuator pushes/

pulls 2 times (unexpected 

stall) trying to remove the 

possible obstacle. After 2 

tries an alarm is signalled 

and the actuator moves to 

initial position and does not 

respond to control signal. 

Stroke value is not updated 

because out of range

The actuator pushes/pulls 

2 times against endpoint 

during calibration and the 

actuator moves to the initial 

position and then it does not 

respond to the control signal. 

The actuator keeps the 

previous stroke

Valve with a 

stroke length 

lower than 

5mm

Remove 

power and 

power up 

again

2

RED LED 

quick 

bl 

GREEN ON

Stroke longer 

than 60mm

Calibration/first 

installation

The actuator exits the 60mm 

stroke range and it moves 

toward the new stroke limit 

signalling an anomaly. The 

actuator pushes/pulls 2 times 

against the new stroke limit, 

then it goes back to the 

initial position still signalling 

the anomaly until it is not 

within 60mm. The actuator 

does not calibrate the stroke 

after 10s (wrong range)

The actuator exits the 60mm 

stroke range and it moves 

toward the new stroke limit 

signalling an anomaly. The 

actuator pushes/pulls 2 times 

against the new stroke limit, 

then it goes back to the 

initial position still signalling 

the anomaly until it is not 

within 60mm. The actuator 

does not calibrate the stroke 

after 10s (wrong range)

Valve with a 

stroke length 

longer than 

60mm

Remove 

power and 

power up 

again

3

RED Quick 

Blinking 

Unexpected 

stall within the 

calibrated 

stroke range

NORMAL 

OPERATION

The actuator tries 5 times 

against the new stall 

condition and then after 10s 

the actuator updates the 

new stroke length

The actuator tries 5 times 

against the new stall 

condition. At the end of the 

attempts the fault will be 

signalled. The actuator does 

not update the new stroke 

length, but after 60s makes 

other attempts to verify the 

stall condition

Valve stuck

Inverted 

control 

signal

4

RED Quick 

Blinking 

Stroke 

longer than 

expected

NORMAL 

OPERATION

The actuator moves toward 

the new stall condition with 

a lower speed; after 10s the 

actuator updates the new 

stroke value

The actuator moves toward 

the new stall condition with 

a lower speed; after 10s the 

actuator does not update 

the new stroke value

Stem 

connection 

loose or 

valve 

damaged

Inverted 

control 

signal

5

RED slow 

Blinking

Low Power 

Voltage

NORMAL 

OPERATION

The actuator is still working 

but performance cannot be 

guaranteed

The actuator is still working 

but performance cannot be 

guaranteed

1. Wrong 

transformer 

size

Correct 

Voltage 

Power

2. Unstable 

power

6

RED slow 

Blinking

High Power 

Voltage

NORMAL 

OPERATION

The actuator is still working 

but performance cannot be 

guaranteed

The actuator is still working 

but performance cannot be 

guaranteed

1. Wrong 

transformer 

size

Correct 

Voltage 

Power

2. Unstable 

power

1

a

 Emissione / 1

st

 Issue rev. d

03/2020

7

DIM265

Содержание MVE5 R Series

Страница 1: ...TAGGIO MOUNTING INSTRUCTIONS Servocomandi per valvole con dispositivo di ritorno in emergenza Valve actuators with emergency fail safe function INSTALLAZIONE INSTALLATION 177 194 122 234 194 86 122 T fluido fluid 120 C T fluido fluid MAX 120 C T fluido fluid 120 C MVE5xxR MVE5xxR 65 1a Emissione 1st Issue rev d 03 2020 1 DIM265 1 2 3 4 ...

Страница 2: ...anneg giare i componenti elettronici sulla scheda Note To avoid damages to electronic components caused by the PCB bending do not press too much while fixing the terminal block L1 Ln 0 V 24Vac dc N4170 04 U Y M Y1 Y2 K1 K2 KC1 K1 K2 KC1 End point position End point position DMVE RELE DI CHIUSURA RELE DI APERTURA K3 K4 KC2 Posizione di fine corsa Posizione di fine corsa K3 K4 KC2 OPENING RELAY CLOS...

Страница 3: ... gato un trasformatore usato anche da altri dispositivi che utilizzino un raddrizzatore a doppia semi onda non isolato 3 point floating control Sink connection Controller 3 point floating control sink connection 0V Y2 Ln MVE Y1 OPEN 24Vac 24Vdc L1 CLOSE 3 point floating control Source connection 3 point floating control source connection 24Vac 0V Controller OPEN CLOSE MVE L1 Ln Y1 Y2 Modulating co...

Страница 4: ...limentazione oppure agire sulla manopola del comando manuale Impostazioni di fabbrica DIP SWITCHES AND JUMPER SETTINGS Set the DIP switches according to the tables here below In order to be sure that any modification has been accepted by the actuator power down and power up it again or act on the manual operation handle to be sure that settings will be recognized open jumper retracted joint closed...

Страница 5: ...ruttore in ON in presenza di scontro inatteso o extra corsa il servocomando non aggiornerà la corsa U 2V U 10V U feedback U 10V U 2V Y1 U feedback Dip switch OFF ON 1 Direct Action Reverse Action 2 Modulating Control MOD Input between Y and M 3 point floating INC Y1 open extend Y2 close retract connected L1 or Ln if powered in Vac if powered in Vdc connected necessarily to Ln 3 Selection of sequen...

Страница 6: ...va corsa dopo 10s Range errato Perdita del linkage o valvola non adatta corsa superiore a 60mm Spegnere Il servocomando e ripetere la fase di calibrazione 3 ROSSO LAMPEGGIANTE VELOCE Scontro inatteso entro il range di corsa calcolato IN FUNZIONAMENTO NORMALE Il servocomando verifica la condizione di stallo per 5 volte Al termine dei tentativi segnala anomalia Il servocomando apprende la nuova cors...

Страница 7: ...still signalling the anomaly until it is not within 60mm The actuator does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and power up again 3 RED Quick Blinking Unexpected stall within the calibrated stroke range NORMAL OPERATION The actuator tries 5 times against the new stall condition and then after 10s the actuator updates the new strok...

Страница 8: ...a 3 ROSSO VERDE LAMPEGGIANTE ALTERNATO Il servocomando sta apprendendo la corsa o sta effettuando il posizionamento iniziale 4 ROSSO VERDE FISSO Comando manuale inserito il servocomando ignora il segnale di comando ATTENZIONE La scheda è alimentata 5 ROSSO VERDE LAMPEGGIANTE SIMULTANEO Il servocomando è in fase di ritorno in emergenza N LEDs behaviour Actuator status 1 GREEN ON The actuator arrive...

Отзывы: