U=10V

Y1

Y2

U = 10V

U = 2V

U= feedback

U= feedback

U = 2V

DIP SWITCHES SETTINGS

Set the DIP switches according to tables below. Power down and 

power up again the actuator or act on the manual override handle 

to be sure that settings will be recognized.

Factory settings

DIP

switch

OFF

ON

1

Direct Action

Reverse Action

2

Modulating Control (MOD) (Input between Y [+] and M [-])

3 point floating (INC) ( Y1 open-extend , Y2 close-retract 

connected to M)

3

-

Selection of sequence mode, control range defined by DIP n. 

5

4

Modulating Control 0-10Vdc

 

(DIP n. 2 OFF only)

Modulating Control 2-10Vdc

 

(DIP n. 2 OFF only)

5

Sequence Control 0-5Vdc with DIP n. 4 OFF only

 

Sequence Control 2-6Vdc with DIP n. 4 ON only

 

(DIP n. 3 ON only)

Sequence Control 5-10Vdc with DIP n. 4 OFF only

 

Sequence Control 6-10Vdc with DIP n. 4 ON only

 

(DIP n. 3 ON only)

6

Voltage Input Signal Vdc

 

(input between Y [+] and M [-])

Current Input Signal 4-20mA (input between Y [+] and M [-]).

 In this case DIP n. 4 must be set to ON.

7

Automatic Calibration: the actuator updates the stroke range 

if an unexpected mechanical stop is detected for at least 10s

Manual Calibration: the actuator calibration is started moving 

the DIP from OFF to ON or vice versa. With DIP in ON in case 

of extra stroke or if an unexpected endpoint is detected, the 

actuator will never update the stroke 

1

st

 Issue rev. c

06/2020

DBL561e

Page 5

Содержание MVE2-65 Series

Страница 1: ...odulating or proportional signal with field selectable range e g 0 10Vdc 2 10Vdc 0 5 2 6Vdc 5 10 6 10Vdc and 4 20mA Manual Override There is a manual operation handle on the actuator When it is low er...

Страница 2: ...s for valves with stroke from 25 to 60 mm Increase decrease 60 s Stroke 5 60 mm limited to 30 mm for MVE2xxS 65 Force 400 N 600 N 1000 N 1500 N 2200 N Duty cycle max 50 60 minutes Analogue input Y M v...

Страница 3: ...olli valves except for 2 3TGB F PN16 VSXT09PBP VSXT10PBP only with MVE204S 65 2 3TGB F PN16 Controlli valves with threaded M40 connections except for VSB VMB VSB F VMB F PN16 with AG51 VSB VMB VSB F V...

Страница 4: ...1 F M N Neutral Modulating Control o 10 Vcc Modulating Control 0 10Vcc 230Vac Controller Command Command MVE M Y F N Neutral Note To avoid damages to electronic components caused by the PCB bending do...

Страница 5: ...DIP n 2 OFF only 5 Sequence Control 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 OFF only Sequence Control 6 10Vdc w...

Страница 6: ...nitial position still signalling the anomaly until it is not within 60mm The actuator does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and p...

Страница 7: ...tor arrived at the extreme point of the stroke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is...

Отзывы: