TERMINAL BLOCK
230~V ±10%
*
F
N
U Y M Y1 Y2
Floting only sink (connect Y1, Y2 to M)
*
(*) In order to use the floating control the only possible connection is
between terminal M and Y1/Y2. Do not connect Y1/Y2 to phase
(F) or neutral (N).
SAFETY PRESCRIPTIONS
230 V products
•
Install on the power supply line a protecting device to avoid
short circuits (fuse or magneto-thermic) according to the spec
-
ifications in force;
•
in case of accidental removal of the cover to make sure that
power is disconnected before working on the actuator or near it;
•
the products are maintenance free.
WIRING DIAGRAMS
3-point Floating Control
230Vac
3-point Floating Control
Controller
Open
Close
MVE
Y2
Y1 F
M
N
Neutral
Modulating Control (o-10 Vcc)
Modulating Control (0-10Vcc)
230Vac
Controller
C
Command -
MVE
M
Y
F
N
Neutral
Note: To avoid damages to electronic components caused by the
PCB bending, do not press too much while fixing the terminal
block.
GROUND CONNECTIONS
Connect the ground terminal to the proper screw labelled with the
ground symbol as shown in the picture here below.
ground terminal
Label
Description
Function
Wire Size
Max wire
Length
F
230Vac
Power Supply
AWG16
(min 1mm
2
-
max 1.5mm
2
)
75m
N
Y
0..10Vdc
Modulating
Control Input
AWG20
(min 0.5mm
2
-
max 1.5mm
2
)
200m
M
0V (Com
-
mon)
Y1
Open
Floating Con
-
trol Input
AWG20
(min 0.5mm
2
-
max 1.5mm
2
)
200m
Y2
Close
V+
16 Vdc
Voltage
Output (max
25mA)
AWG20
(min 0.5mm
2
-
max 1.5mm
2
)
200m
M
0V (Com
-
mon)
U
2÷10Vdc
Feedback
Output Signal
AWG20
(min 0.5mm
2
-
max 1.5mm
2
)
200m
M
0V (Com
-
mon)
1
st
Issue rev. c
06/2020
DBL561e