background image

TERMINAL BLOCK

230~V ±10%

*

F

N

U Y M Y1 Y2

Floting only sink (connect Y1, Y2 to M)

*

(*) In order to use the floating control the only possible connection is 

between terminal M and Y1/Y2. Do not connect Y1/Y2 to phase 

(F) or neutral (N).

SAFETY PRESCRIPTIONS

230 V products

 

• 

Install  on  the  power  supply  line  a  protecting  device  to  avoid 

short circuits (fuse or magneto-thermic) according to the spec

-

ifications in force;

• 

in case of accidental removal of the cover to make sure that 

power is disconnected before working on the actuator or near it;

• 

the products are maintenance free.

WIRING DIAGRAMS

3-point Floating Control

230Vac

3-point Floating Control

Controller

Open
Close

MVE

Y2

Y1 F

M

N

Neutral

Modulating Control (o-10 Vcc)

Modulating Control (0-10Vcc)

230Vac

Controller

C
Command -

MVE

M

Y

F

N

Neutral

Note:   To avoid damages to electronic components caused by the 

PCB bending, do not press too much while fixing the terminal 

block.

GROUND CONNECTIONS

Connect the ground terminal to the proper screw labelled with the 

ground symbol as shown in the picture here below.

 

ground terminal

Label

Description

Function

Wire Size 

Max wire 

Length

F

230Vac

Power Supply

AWG16

 

(min 1mm

max 1.5mm

2

)

75m

N

Y

0..10Vdc

Modulating 

Control Input

AWG20

 

(min 0.5mm

2

 - 

max 1.5mm

2

)

200m

M

0V (Com

-

mon)

Y1

Open

Floating Con

-

trol Input

AWG20

 

(min 0.5mm

2

 - 

max 1.5mm

2

)

200m

Y2

Close

V+

16 Vdc

Voltage 

Output (max 

25mA)

AWG20

 

(min 0.5mm

2

 - 

max 1.5mm

2

)

200m

M

0V (Com

-

mon)

U

2÷10Vdc

Feedback 

Output Signal

AWG20

 

(min 0.5mm

2

 - 

max 1.5mm

2

)

200m

M

0V (Com

-

mon)

1

st

 Issue rev. c

06/2020

DBL561e

Page 4

Содержание MVE2-65 Series

Страница 1: ...odulating or proportional signal with field selectable range e g 0 10Vdc 2 10Vdc 0 5 2 6Vdc 5 10 6 10Vdc and 4 20mA Manual Override There is a manual operation handle on the actuator When it is low er...

Страница 2: ...s for valves with stroke from 25 to 60 mm Increase decrease 60 s Stroke 5 60 mm limited to 30 mm for MVE2xxS 65 Force 400 N 600 N 1000 N 1500 N 2200 N Duty cycle max 50 60 minutes Analogue input Y M v...

Страница 3: ...olli valves except for 2 3TGB F PN16 VSXT09PBP VSXT10PBP only with MVE204S 65 2 3TGB F PN16 Controlli valves with threaded M40 connections except for VSB VMB VSB F VMB F PN16 with AG51 VSB VMB VSB F V...

Страница 4: ...1 F M N Neutral Modulating Control o 10 Vcc Modulating Control 0 10Vcc 230Vac Controller Command Command MVE M Y F N Neutral Note To avoid damages to electronic components caused by the PCB bending do...

Страница 5: ...DIP n 2 OFF only 5 Sequence Control 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 OFF only Sequence Control 6 10Vdc w...

Страница 6: ...nitial position still signalling the anomaly until it is not within 60mm The actuator does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and p...

Страница 7: ...tor arrived at the extreme point of the stroke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is...

Отзывы: