background image

red as active, the local one to the NR controller connected to input 

S1 (return sensor).

Pressing  the  knob  displays  the  Error  and  Modbus  Address  page  of 

the controller

Error page

Error code display:

ERROR 

CODE

DESCRIPTION

1

Room sensor communication

2

Modbus communication

4

Recovery sensor

8

Remote set correction

The error displayed will be an OR of the active error codes.

Modbus Address Page

Display of Modbus controller address NR9001.

The permanence in a page without any action for more than 10

seconds returns to the stationing page.

Buttons

ON/OFF” button: allows the regulation to be switched off, switching 

from the Comfort mode (NM) to the off mode (FA). When the con-

troller is off, the word “OFF” is displayed instead of the room tempe-

rature display.

Mode

”  button:  if  enabled  by  configuration,  it  allows  switching  to 

reduced speed (RF), displaying the word “ECO” instead of displaying 

the time.

FAN

” button: if enabled by the configuration, it allows you to ma

-

nually select one of the 3 + OFF speeds. If “Auto” operation is set, the 

fan speed is automatically determined by the controller. In the latter 

case all speed s the word “Auto” will be lit.

Clock

” button: if enabled by the configuration, it allows to activate 

the  time  program  (locally  configured  to  the  sensor).  The  time  pro

-

gramming will determine a set temperature defined for each sche

-

duled time slot. If a time slot is OFF, the controller will be off.

The activation of the time program prohibits the possibility of setting 

the knob set.

Furthermore, a long press on the key allows entering the configura

-

tion to set the time and the time programs.

Knob

” button: depending on the configuration, the key can be ro

-

tated to set the temperature set (between the minimum value and 

the maximum value set by the configurator) or make a correction 

(+ - the value set by the configurator) of the Set in EEPROM memory 

area (always from the configurator). The resolution is 0.1.

Furthermore, by pressing the “Knob” it is possible to display, cyclical-

ly, the alarm error code, the Modbus address of the controller and 

the main page.

ON / OFF” + “FAN” buttons: a long press of the two buttons allows 

entering the configuration to be able to set the Modbus communi

-

cation parameters (Baud and Address) and the calibration of the 

temperature sensor (Pcal).

In the lower part the following “symbols” may appear:

• 

Bell - indicates the presence of an alarm in the controller.

• 

Snowflake - indicates that the controller is adjusting to give Cold 

(control Loop F output> 0)

• 

Flame

  -  indicates  that  the  controller  is  adjusting  to  give  Heat 

(control Loop C output> 0)

STA70M SENSOR

STA70M sensor is a room terminal that allows the user to control the 

temperature in a residential environment. It communicates with the 

Modbus protocol and can be connected to the NR9001 controller. 

The power supply can be 24 Vac/dc.

Setting Communication Parameters

STA70M sensor requires a preconfiguration for the 

Modbus communication and the parameters to be 

managed in order to be connected on the 485 bus 

of the NR9001 controller.

Enter  the  configuration  by  selecting  the  icon 

 

and the settings page will be displayed.

Select the ModBus icon 

: the Modbus page will 

be displayed.

To change the data enter the password = 1909. 

Enter the following data: 

• Address

 Modbus = 1. 

• Baud rate

 = 9600. 

• Parity

 = NO. 

• Stop bit

 = 1. 

• Timeout

 = 10. Time out for connection status

• Reboot

 = No. Forced sensor reboot. 

The STA70M sensor offers different display modes 

and different functions that can be enabled or di-

sabled directly by the sensor by accessing the “Pa-

ram” page.

2-4 pipe system configuration

The selection of 2-4 pipes involves the display on the sensor of 2 or 4 

sets (Set C, Set C Eco, Set F, Set F Eco).

Operate as follows to configure the sensor:

1.  Switch off the controller;

2.  On the sensor go into settings and set the address of the con-

troller = 0;

3. 

Set, by dipswtch or supervisor, if the controller must function as 

2 or 4 pipes;

4. 

Power back the controller;

5.  STA.M sensor is reinitialized.

Display Configuration

Through the configurator it is possible to choose between 4 different 

1

st

 Issue

06/2019

DBL585e

Page 18

Содержание Energon NR9001

Страница 1: ...have a different meaning if changeover auto instead of Aux Loop function is disabled from the configuration tool S4 sensor is used to switch the controller operation mode to Energon Fan Coil Digital C...

Страница 2: ...set at 9013 ModBus address 1 BUS output for Modbus supervisor connection 1 BUS output for STA60M or STA70M sensor connection For any customizations related to the controller configuration con tact th...

Страница 3: ...I3 input digital 3 24Vac Summer Winter contact 37 DI4 input digital 4 24Vac Comfort economy contact 36 DI_COM input digital COM COM 35 S1 input analogue input Return sensor 34 S2 input analogue input...

Страница 4: ...of 4 pipe plant with 230V 3 point valves Example of 4 pipe plants with 230V ON OFF valves 1st Issue 06 2019 DBL585e Page 4 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Change...

Страница 5: ...pe plants with 24V 3 point valves Example of 4 pipe plant with 24V ON OFF valves 1st Issue 06 2019 DBL585e Page 5 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Страница 6: ...e plant with 230V 3 point valves Example of 2 pipe plant with 230V ON OFF valves 1st Issue 06 2019 DBL585e Page 6 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Страница 7: ...pe plant with 24V 3 points valves Example of 2 pipe plant with 24V ON OFF valves 1st Issue 06 2019 DBL585e Page 7 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Страница 8: ...0 copper wire plait type twisted shielded braided and insulated The shield must be connected to controller GND pin 25 The network must be wired only in accordance with the principle shown here called...

Страница 9: ...e the regula tion If the fan is connected to the relay output it is necessary to set the minimum fan speed parameter at 1 A system configuration with Proportional Fan requires setting the minimum spee...

Страница 10: ...sed in parallel In case of use of 3 speed fans 3 relays the 0 10V outputs are always available and they follow the ON OFF or 3 point valves characteris tics The diagrams of the valves and fans share t...

Страница 11: ...Propor tional Band as shown in the diagram aside 2 ON OFF Valves and 3 Speed FAN The valves are activated in ON OFF mode with a hysteresis Speed 1 2 and 3 follow to the Pro portional Band as shown in...

Страница 12: ...alves 3 point or 0 10V and 3 speed fan The valves are activated in Pro portional mode 0 100 using a proportional band Speed 1 follows to the Proportion al Band as shown in the diagram aside 6 ON OFF V...

Страница 13: ...llow the Proportion al Band as shown in the diagram aside generating a 0 10V output control signal 7b 0 5 6 10 V Sequence Valves and Proportional Speed Fan 0 10V 4 pipe plant The valves are activated...

Страница 14: ...luid is the RED LED NR9001 CONTROLLER DIP SWITCHES AND LEDs The controller has 8 DIP switches accessible by removing the top co ver and 2 LEDs to identify the state of the valves open or closed and th...

Страница 15: ...Automatic changeover min set 10 35 20 Automatic changeover max set 10 35 30 Fan min limit set 10 55 35 Fan min limit hysteresis 0 10 3 Operation Mode COMFORT 0 Economy 1 Frost 2 0 2 0 COMFORT Delay T...

Страница 16: ...nt display STATUS WORD parameter NR9001 BIT Description 0 1 Default 0 Operation Mode Remote Disable digital input Comfort Economy and Power Off Local Enable digital input Comfort Economy and Power Off...

Страница 17: ...of the schedule consists of setting the desired Tem perature Set for each band In addition to the Set there is also the possibility of setting the OFF sta tus which for the controller has the meaning...

Страница 18: ...g the Knob it is possible to display cyclical ly the alarm error code the Modbus address of the controller and the main page ON OFF FAN buttons a long press of the two buttons allows entering the conf...

Страница 19: ...e The parameters Dead band and Set Economy allow to determi ne the Set of Cold Set of Hot Dead band the set in Eco C Set C Rid Set the Eco Set F Set F Rid Set Instead for a more inuitive management th...

Страница 20: ...ed in EEPROM memory The address can be changed only if the controller Dipswitch is not active If the STA70M sensor is present the Modbus address cannot be set by Supervision Contact our technical secr...

Страница 21: ...performances stated in this sheet can be modified without any prior notice DIMENSIONS mm NR9001 STA60M STA60M 2 STA60MP STA60MP 2 86 86 8 22 55 28 48 74 60 74 60 1st Issue 06 2019 DBL585e Page 21 STA...

Отзывы: