Cr:0 is continuous operation (no cycling), with a variance of +/- 0.3ºC (+/- 0.6ºF). The heating unit will operate at full
power and the power bar icon will appear full. This function is for users who do not want their electric heating devices
to turn on and off frequently.
Cr:1 is a 20-seconds cycle rate with proportional heating. This means the heating will turn on and off once every 20
seconds to provide a stable room temperature. This cycle rate allows a proportional level of power to the heating
device. This is indicated on the thermostat display by the power bar icon being partially filled, indicating the amount
of power going to the heater. This setting is recommended for standard electric heating devices, without fans, and will
provide the most energy-efficient heating and a stable temperature.
Cr:2 is a 240-second cycle rate. This means the heating will turn on and off once every 240 seconds.
This is the recommended setting for fan assisted heaters and radiant floor/ceiling heating devices.
Pre-comfort Recovery supplementary information
This thermostat is equipped with a "Pre-comfort Recovery" feature that will activate the heating system in advance of
the actual set program time so that the room will be at the desired temperature at the start of the program time.
It is normal for the system to be activated earlier than the actual set program time (up to one hour).
The pre-comfort recovery can be disabled if desired. If pre-comfort recovery is turned off (rE:0), heating will only be
initiated at the exact start time of the program period.
Setup