CTI 2500-RBC Installation and Operation Guide V1.6
38
Data transfer rate
in kbit/s
9.6 19.2
45.45 93.75 187.5 500
1500
3000
6000
12
000
Max segment
length in meters
120
0
1200
1200
1200
1000
400
200
100
100
100
Important:
In a PROFIBUS-DP/FMS installation, you must choose a data transfer rate which is
supported by all devices connected to the bus. The chosen data transfer rate then determines the
maximum segment lengths as shown above.
The maximum admissible distance between two bus stations in each PROFIBUS network can be
calculated as follows:
( 1) * Segment length
NO_REP= The maximum number of repeaters connected in series (depends on repeater type).
Bus termination
In order to minimize cable reflections and ensure a defined noise level on the data lines, the data transfer
cable must be terminated at both ends with a terminating resistor combination as follows
.
Bus connectors and PROFIBUS-DP/FMS interface
A bus connector is used to connect the bus cable to the PROFIBUS device. Bus connectors are
available with a variety of protection classes and mechanical designs. The choice of connector is
mainly determined by the space available in the vicinity of the PROFIBUS device (i.e. PC interface,
PLC or special fieldbus device). EN 50170 Volume 2 recommends the use of a 9-pin Sub-D
connector. Depending on the required protection class and the application of the fieldbus device, other
connector designs are also allowed. The table below shows the pin assignment if a 9-pin Sub-D connector is
used: