Scroll through the module list to find the 2500 or 505 series devices. Select the desired module for
I/O slot #1 and then press the
Add Module
button. Then select the module for each of the remaining
slots and add them in like manner. Note: All empty slots before an occupied slot must be filled with a
“Blank” entry. Any empty slots after the last occupied slot does not have to have a “Blank” entry.
Each module in the remote base needs a unique starting I/O address. You can enter the starting I/O
address of a module by clicking on the address field on the module row.
Modules that use X and Y memory must have unique addresses because X and Y variables share the
same memory table on the CPU. An ‘X32’ and a ‘Y32’ cannot coexist in the same program.
Likewise, modules that use WX and WY memory must have unique memory addresses assigned.
However, because WX/WY memory is separate from X/Y memory, it is completely acceptable to
have both a X32 and a WX32 in the same program.