Tuning Procedures
Initial Test Settings
When running the tests outlined in this section, the motor and drive must be operational so
you will need to enter starting values.
If your application has less than a 10:1 inertia mismatch, the default parameter settings will
be acceptable. If the inertial mismatch is greater than 10:1, use the following table for initial
parameter settings.
Determining Friction
This parameter represents friction that increases proportionally as motor velocity increases.
The viscous friction of your system can be determined by reading the percent of continuous
torque required to operate the loaded motor at two different speeds.
Consider the following before determining the Friction:
•
The most consistent readings can usually be obtained at motor speeds higher than 500
RPM but lower test speeds can be used if necessary.
•
If your application has travel limits, it may be helpful to use an external position controller
to prevent the axis from exceeding the machine limits. Set up a trapezoidal profile as
shown.
•
In the procedure below, the Torque Command and Velocity Feedback parameters can be
measured using the drive’s analog outputs, PowerTools software or an FM-P.
•
With vertical loads the test readings must be taken while traveling in the same direction.
•
An oscilloscope may be needed for systems with limited travel moves to measure the
rapidly changing torque and velocity signals.
•
If your system’s friction changes with operating temperature, perform this procedure at
normal operating temperature.
Procedure for Determining Friction:
1.
Run the motor at the low test speed (at least 500 RPM).
2.
While at speed, note the Torque Command Actual value (TCL).
Parameter
Setting
Friction
0.00
Inertia Ratio
1/3 to 1/2 Actual
Response
500/Inertia Ratio
High Performance Gains
Disabled
Feedforwards
Enabled
Line voltage
Actual Applied
Содержание FM-3
Страница 2: ......
Страница 14: ...xii ...
Страница 16: ...2 FM 3 Programming Module Reference Manual Figure 2 FM 3 Programming Module Features ...
Страница 128: ...114 FM 3 Programming Module Reference Manual ...
Страница 156: ...142 FM 3 Programming Module Reference Manual ...
Страница 196: ...182 FM 3 Programming Module Reference Manual ...
Страница 238: ...224 FM 3 Programming Module Reference Manual ...
Страница 251: ...237 Diagnostics and Troubleshooting Figure 97 Diagnostic Cable DGNE Diagram ...
Страница 262: ...248 FM 3 Programming Module Reference Manual ...
Страница 264: ...250 FM 3 Programming Module Reference Manual AX4 CEN CDRO ...
Страница 265: ...251 Specifications Cable Diagrams ...
Страница 266: ...252 FM 3 Programming Module Reference Manual SNCE XXX Cable SNCDD 001 5 Cable ...
Страница 267: ...253 Specifications SNCO 003 Cable SNCI 003 Cable ...
Страница 268: ...254 FM 3 Programming Module Reference Manual SNCLI 003 Cable ...
Страница 271: ...257 Specifications CDRO XXX Cable 8 9 24 23 38 37 11 12 34 16 14 15 29 4 19 26 40 18 17 31 33 43 44 41 27 ...
Страница 272: ...258 FM 3 Programming Module Reference Manual TIA XXX Cable DDS XXX Cable ...
Страница 274: ...260 FM 3 Programming Module Reference Manual CMDS XXX Cable CMMS XXX Cable ...
Страница 275: ...261 Specifications CFCS XXX Cable ...
Страница 276: ...262 FM 3 Programming Module Reference Manual CFCO XXX Cable ...
Страница 277: ...263 Specifications CFOS XXX Cable ...
Страница 278: ...264 FM 3 Programming Module Reference Manual ...
Страница 286: ...272 FM 3 Programming Module Reference Manual ...
Страница 290: ...276 FM 3 Programming Module Reference Manual ...
Страница 291: ......