Restart_Notification_Recipients
(202)
List of BACnetRecipient
Time_Of_Device_Restart (203)
BACnetTimeStamp
Vendor Specific Object Properties:
Physical I/O Assignment (881)
(W)
BACnetObjectIdentifier
Index: 1..MAX_HARDWARE_POINT
MSTP_Port_Baud_Rate (1201)
(W)
ENUMERATED:
(9600, 19200, 38400, 76800)
NOTE: Changes to port settings will take effect
only after a COLDSTART or
WARMSTART command is issued.
MSTP_Station_ID (1202) (W)
Unsigned
Enable_Auto_Reset (1203) (W)
BOOLEAN
(True if reliability codes should auto return to
zero)
Reinit_Password (1205) (WO)
CharacterString
Note: This property is write-only, and is only
writeable with unlock sequence.
Password_Unlock (1206) (W)
Unsigned
Note: Must write device’s own device instance to
this property to unlock password for writing, and
next property written must be 1205. Any other
sequence will reset and lock out password write.
Device_Allocation (1251) (W)
Unsigned
Index: Use object type
analog-input (0)
analog-output (1)
analog-value (2)
binary-input (3)
binary-output (4)
binary-value (5)
multi-state-input (13)
multi-state-output (14)
multi-state-value (19)
(value is count allocated of objects of type
indexed)
(attempting to write a count that is not
acceptable will return error class Services, code
Invalid Configuration Data)
NOTE: After writing all 9 object allocation counts,
12. Object Properties
file:///C:/AAA_CSI/Literature/2016 User Guides/VP4-BACnet User Gui...
6 of 7
11/3/2016 10:43 AM
Содержание ValuPoint 4
Страница 22: ...3 Connect file C AAA_CSI Literature 2016 User Guides VP4 BACnet User Gui 6 of 6 11 3 2016 10 40 AM ...
Страница 28: ...4 Who Is file C AAA_CSI Literature 2016 User Guides VP4 BACnet User Gui 6 of 6 11 3 2016 10 40 AM ...
Страница 33: ...Page 3 of 5 6 Device Page 8 16 2017 mk MSITStore C AAA_CSI Literature 2016 20User 20Guides VP4 BACnet 20Us ...
Страница 56: ...9 Object Map List file C AAA_CSI Literature 2016 User Guides VP4 BACnet User Gui 6 of 6 11 3 2016 10 42 AM ...