24
-
Figure 3.10 – Working range settings.
3.5.1
"MAX. THD I" setting:
1.
Enables disconnection of all the capacitors whenever the
actual THD I value exceeds the value which was defined by
the user. When THD I = 0 this option is disabled.
2.
In order to change the Max. THD-I, scroll to Max. THD-I line
and press "Enter". The Max. THD-I screen appears.
3.
Use the buttons F3 & F4 to move the cursor, to set the value
use buttons F1 & F2, when finished click “ENTER”.
3.5.2
"MAX. THD V" setting:
1.
Enables disconnection of all the capacitors whenever the
actual THD V value exceeds the value which was defined by
the user. When THD V = 0 this option is disabled.
2.
In order to change the Max. THD-V, scroll to Max. THD-V
line and press "Enter". The Max. THD-V screen appears.
3.
Use the buttons F3 & F4 to move the cursor, to set the value
use buttons F1 &F2, when finished click “ENTER”.