18
-
3.3.1
Setting the Power Factor Set Point:
1.
Scroll down to Power Factor and press "Enter".
2.
The Power Factor setting screen appears.
Figure 3.6 – Power Factor change.
3.
Use the buttons F3 & F4 to move the cursor, to set the value
use buttons F1 &F2, when finished click “ENTER”.
3.3.2
Changing the Capacitors Connection Order
:
1.
At the Vital Setting screen scroll down to "ORDER".
2.
Each time you press Enter at the line indicating "ORDER",
the connection order options will be changed from the
following possibilities: "RANDOM", "FIRST", "CYCLE".
3.
The capacitors chosen for power factor correction are chosen
according to their size, meaning that it chose the minimal
number of the capacitors for achieving the requested value of
the power factor.