23

 

-

  

 

3.

 

Use the buttons F3 & F4 to move the cursor, to set the value 
use buttons F1 & F2, when finished click “ENTER”. 

 

3.4.3

 

"CONTROL RANGE":  

1.

 

Control Range enables the user to define the working range of 
the capacitors in performing power factor correction. When 
the "control range" = 0.01 the system is looking for the 
minimal capacitors number for performing power factor 
correction from the desired value (for example, 0.92) to the 
value 0.93 = 0.92+0.01 (control range). From this point, the 
system is looking for the minimal capacitors' combination 
required, for reaching the power factor of 0.93 and its 
disconnecting capacitors accordingly. 

2.

 

In order to change Control Range scroll to Control Range line 
and press "Enter". The Delay Control Range screen appears. 

3.

 

Use the buttons F3 & F4 to move the cursor, to set the value 
use buttons F1 & F2, when finished click “ENTER”. 

 

3.5

 

Working range settings 

Working range settings enable defining limits for current, 
voltage, THD V and THD I values

In order to define the Working Range Setting, you must access 
the Setting screen by repeating steps from chapter 3.1, paragraphs 
1,2,3. 

1.

 

Once the Setting screen appears, scroll to Working Range and 
press "Enter". The Working Range screen appears. 

 

 

Содержание Elnet PFC

Страница 1: ...PFC Elnet Power Factor Controller Rev 1 4...

Страница 2: ...Screen 8 CHAPTER 2 Power Factor Controller 10 2 1 General Information 10 2 2 Controller s Data Screen 11 2 3 Voltage Current Hz 12 2 4 Power Factor THD 12 CHAPTER 3 Power Factor Controller Settings 1...

Страница 3: ...ternally on the rear of the instrument and the lead from the leg of the external Current Transformer must pass through in the correct direction NOTE Ensure all the connections to the leads of the curr...

Страница 4: ...epeat the procedure for Line 2 and Line 3 I2 I3 K 3 Connect the rest of the connections to the ElNet PFC Power Factor Controller by means of terminal connector plugs All Rear Panel connections are acc...

Страница 5: ...ing Diagrams Figure 1 1 Three Phase Electrical wiring diagram Notice The distance between the external current transformer and the Elnet will not exceed 5m Attention Maximum current for contactors R1...

Страница 6: ...6 Notice The distance between the external current transformer and the Elnet will not exceed 5m Figure 1 2 Single Phase Electrical wiring diagram...

Страница 7: ...mer on Line1 Note the correct direction to insert the lead I2 From external Current Transformer on Line2 Note the correct direction to insert the lead I3 From external Current Transformer on Line3 Not...

Страница 8: ...press Enter Figure 1 4 Access the Settings screen 2 The ENTER CODE screen appears Figure 1 5 Enter Code screen 3 The password to activate the Test Relay screen is 789 4 Use the buttons F3 F4 to move t...

Страница 9: ...5 The TEST RELAY screen will appear Figure 1 6 Test Relay screen 6 Use the navigation buttons to force and release the relevant output 7 When finished hold the Back pushbutton until the main menu appe...

Страница 10: ...n of capacitors size and its connection in various methods ElNet PFC Main Menu includes the following functions Figure 2 1 Main Menu Controller s data screen enables displaying the readings of power f...

Страница 11: ...ppears Low Current Appears in case of measured current is lower than in the allowed Working range definitions High THD Appears in cases of measured current voltage THD is higher than in the allowed Wo...

Страница 12: ...e Voltage Current Hz menu and press Enter the Voltage screen appears Figure 2 3 Voltage Current Hz 2 Use the F1 F2 F3 pushbuttons to choose the monitored on screen data Voltage Current Frequency 2 4 P...

Страница 13: ...Menu scroll to the Power Factor THD menu and press Enter the Power Factor screen appears Figure 2 4 Power Factor screen 2 Pressing on F1 THD V F2 THD I buttons allow to access the THD data screens Fi...

Страница 14: ...Non Vital Setting Working Range 3 1 Single Three Phase modes 1 Setting the PFC to operate in single phase or three phase mode will effect only on the screen appearance the rest of the features and set...

Страница 15: ...3 2 Settings 5 Scroll to TYPE and click Enter in order to change the mode between single phase and three phases 3 2 Transformers Ratio 1 From Main Menu scroll to SETTING and press Enter The Enter Code...

Страница 16: ...Transformer Ratio and press Enter The Transformer Ratio screen appears 4 In order to set the Current Transformers ratio scroll to Current Trans and press Enter Figure 3 3 Transformer Ratio 5 The Curre...

Страница 17: ...Enter 8 Use the buttons F3 F4 to move the cursor to set the value use buttons F1 F2 when finished click ENTER 3 3 Vital Setting In order to define the Vital Setting you must access the Setting screen...

Страница 18: ...k ENTER 3 3 2 Changing the Capacitors Connection Order 1 At the Vital Setting screen scroll down to ORDER 2 Each time you press Enter at the line indicating ORDER the connection order options will be...

Страница 19: ...and third and so on this method is recommended in places preferring unequal working hours of the capacitors CYCLE whenever there are a few capacitors of equal size there is a possibility to use the c...

Страница 20: ...re 1 The Elnet PFC enables true capacitors value measure for capacitors 1 up to 6 2 In order to measure and automatically define the values of the capacitors which are used in the system at the Vital...

Страница 21: ...d of the values entered by the user at the previous screen capacitors value 3 3 5 Capacitor s steps 1 In order to set the number of the capacitors steps in the system at the Vital Setting screen scrol...

Страница 22: ...roll to DELAY ON and press Enter The Delay On screen appears 3 Use the buttons F3 F4 to move the cursor to set the value use buttons F1 F2 when finished click ENTER 3 4 2 DELAY OFF 1 Delay Off enables...

Страница 23: ...imal capacitors combination required for reaching the power factor of 0 93 and its disconnecting capacitors accordingly 2 In order to change Control Range scroll to Control Range line and press Enter...

Страница 24: ...screen appears 3 Use the buttons F3 F4 to move the cursor to set the value use buttons F1 F2 when finished click ENTER 3 5 2 MAX THD V setting 1 Enables disconnection of all the capacitors whenever t...

Страница 25: ...les defining voltage low limit value under this value all the capacitors will be disconnected 2 In order to change the Min Voltage scroll to Min Voltage line and press Enter The Min Voltage screen app...

Отзывы: