PARAMETERS
GENERAL SETTINGS
001 POWER SUPPLY VOLTAGE
230 Vac
2
115 Vac
1
002 PROCESS INPUTS VOLTAGE
NO INPUTS
0
230 Vac
2
115 Vac
1
48 Vac
8
24 Vac
4
003
BURNER TYPE
GAS
G
OIL
O
004
INPUT TERMINAL 17
THERMOSTAT 2
T
2
nd
STAGE FLAME DETECTOR
F
HI-
TEMP BYPASS
B
005 AIR PRESSURE SWITCH RESPONSE TIME
1” …
01
DEFAULT 1
”
…
3
0”
30
BEHAVIOUR AT POWER ON – LOCKOUT
101 START-UP MODE
AUTOSTART
A
STANDBY
S
102 AIR OUTPUT
ALWAYS OFF
N
ALWAYS ON
Y
CONTROLLED FROM P INPUT
I
CONTROLLED FROM BUS
B
BEHAVIOUR DURING SHUTDOWN
201
MINIMUM BURNER PAUSE TIME
0” …
000
DEFAULT 0”
… 250”
250
202 AIR OUTPUT
ALWAYS OFF
N
ALWAYS ON
Y
CONTROLLED FROM P INPUT
I
CONTROLLED FROM BUS
B
ALL OUTPUTS SWITCHED OFF WHILE IN MANUAL SHUTDOWN
BEHAVIOUR DURING PREPURGE
301 AIR RUN-UP TIME
0” …
000
DEFAULT 0”
… 250”
250
302 AIR OUTPUT
OFF
N
ON
Y
303 PREPURGE (WAITING) TIME
0
” …
000
DEFAULT 1
”
… 250”
250
BEHAVIOUR DURING IGNITION
401
PRE-IGNITION TIME
1
0,5”
402
FIRST SAFETY TIME
2” …
02
DEFAULT 3
”
… 25”
25
403
PILOT BURNER STARTUP ATTEMPTS
1
1
2
2
3
3
4
4
404
PILOT
BURNER FLAME SENSITIVITY
1
µA …
1
USED ALSO FOR DETECTION IN PREPURGE
… 9
µA
9
BEHAVIOR DURING OPERATION
501
PILOT BURNER PROVING PERIOD
1” …
01
DEFAULT 3
”
… 25”
25
502 SECOND SAFETY TIME
NO MAIN
0
1” …
1
… 5”
5
INTERMITTENT PILOT
C
PILOT REMAINS ACTIVE
503
MAIN BURNER FLAME SENSITIVITY
1
µA …
1
… 9
µA
9
504
FLAME FAILURE
LOCKOUT
L
RECYCLE
C
IGNITION RESTORATION
K
505 FLAME FAILURE RESPONSE TIME
1” …
01
DEFAULT 1
”
… 12”
12
506 AIR OUTPUT
ALWAYS OFF
N
FOLLOWS PILOT
P
FOLLOWS MAIN
M
FOLLOWS BOTH PILOT & MAIN
V
CONTROLLED FROM P INPUT
I
CONTROLLED FROM BUS
B
507 AIR FAILURE
LOCKOUT
L
RECYCLE
C
508
MINIMUM COMBUSTION TIME
0” …
00
… 25”
25
509 ALLOWED POST-
COMBUSTION TIME
1
< 20”
BEHAVIOR DURING POSTPURGE
601 AIR OUTPUT
OFF
N
ON
Y
602 POSTPURGE (WAITING) TIME
0
” …
000
DEFAULT 1
”
… 250”
250
COMMUNICATION SETTINGS
701
ZONE (SEGMENT)
0 … 9 a … Z
702 UNIT (NODE)
0 … 9 a … Z
703
BAUD RATE
4800
9600
19200
38400
57600
3
DEFAULT
4800
115200
3
704
TIMEOUT
2
DISABLED
1” …
DEFAULT DISA
B
LED
… 50”
1
NON-
CONFIGURABLE PARAMETER
2
INACTIVE
WHEN THE BURNER IS OFF
3
TraxBus MAY NOT WORK