CHECKSUM CALCULATION
Commands without valid checksum KK are ignored.
The answer includes a valid checksum that can be
optionally evaluated by supervisor.
KK is the ASCII figure of the sum of all c
haracters HEX
values, including Carriage Return. See example and use
only last two characters, ignoring leading ones (if any).
< 0 8 S 04 <Cr>
<
Equals HEX 3C +
0
Equals HEX 30 +
8
Equals HEX 38 +
S
Equals HEX 53 +
<Cr>
Equals HEX 0D =
ASCII
104
COMMAND LIST
a
AIR OFF
TURN OFF THE AIR VALVE (OR FAN) OUTPUT W
HEN MODE BUS IS ENAB
LED
A
AIR ON
TURN ON THE AIR VALVE (OR FAN) OUTPUT WH
EN MODE BUS IS ENABL
ED
H
BURNER
HALT
SHUTDOWN THE BURNER
R
BURNER RUN
RESTART THE BURNER F
ROM SHUTDOWN
§ 1
m
MAIN OFF
TURN OFF MAIN BURNER, BACK TO PILOT BURNER
M
MAIN ON
TURN ON MAIN BURNER
B
UNLOCK
RESET THE BURNER FROM LOCKOUT, MUST BE CONFIRMED
§ 2
Y
UNLOCK CONFIRM
RESET FROM LO
CKOUT
, CONFIRMATION
S
STATUS
NO ACTION BUT STATUS REQUEST
L
FLAME SIGNAL
ACTUAL FLAME CURRENT
STATUS LIST
S
STOP
BURNER LOCKOUT OR FA
ILURE
§ 3
0
MANUAL SHUTDOWN
BURNER OUT OF SERVICE
(MANUAL
SHUTDOWN FROM PUSH BUTTON
)
H
HALT FROM REMOTE
BURNER SHUTDOWN (SWITCHED OFF FROM FIELDBUS)
§ 1
t
HALT FROM THERMOSTAT
BURNER SHUTDOWN
(SWITCHED OFF FROM THERMOSTAT INPUT)
§ 1
A
AIR PRESSURE WAITING
AIR RUN-UP DELAY / AIR PRESSURE WAITING
P
PREPURGE
PREPURGE IN PROGRESS
1
IGNITION
BURNER IGNITION
TRIAL IN PROGRESS
2
PILOT ON
PILOT BURNER ON
3
PILOT & MAIN ON
PILOT & MAIN BURNER ON
4
MAIN ON
MAIN BURNER ON
Y
POSTCOMBUSTION
WAITING FOR FLAME QUENCHING
W
POSTPURGE
POSTPURGE IN PROGRESS
FLAME SIGNAL
LAST MEASURED SIGNAL STRENGTH 1
… 26
µA
§ 4
§1 PRIORITY TO LOCAL THERMOSTAT INPUT.
ONCE THE THERMOSTAT IS ACTIVE, THE REMOTE
FIELDBUS COMMAND IS
EVALUATED.
§2 THE SUPERVISOR MUST SEND A RESET CONFIRMATION WITHIN 25 SECONDS FROM PERIPHERAL
ACKNOWLEDGE TO RESET
COMMAND. AN UNCONFIRMED RESET COMMAND IS CANCELLED AFTER 25 SECONDS.
LOCKOUT WILL BE FORC
ED TO PREVENT DANGEROUS OPERATION RECEIVING AN ILLEGAL RESET COMMAND
(i.e.:
CONFIRMATION BEFORE
RESET).
§3
ALL LOCKOUTS AND FAI
LURES ARE GROUPED WITHIN A SINGLE CODE TO SIMPLIFY THE PARSING. DETAILED INFORMATION
AVAILABL
E FROM THE FRONT PANEL DISPLAY.
ADDITIONAL INFORMATION READING THE LOG FILE STORED INTO THE UNIT.
§
4
SIGNAL STRENGHT RETURNED IN A SINGLE LOWERCASE CHARACER a TO z:
-
→
0 µA
a
→
1 µA
b…y
→
2
… 25 µA
z
→
26 µA OR HIGHER