Instrument Calibration
66
515 BR03 - 15 August 2021
Error Messages
The system displays error messages, and records the associated exception
status code, in the order of highest to lowest priority as listed in the
following table:
Warning Messages
The system displays warning messages as described in the following table:
Error
Messages
Status
Code
Description -
(Highest Priority at top of table).
CPU Card
Failure
20
There are failed components on the CPU card and technical support
is required.
Power Supply
is Low
21
The input and/or output power supply voltage is too low, ensure
that:
(a) input power supply voltage is within the specified range
(b) output power supply is not overloaded.
New/Failed
Battery - Set
Time
22
The real-time clock has lost the correct time because the battery has
failed, or there is a new battery. Set the current time and date (in the
TM/LOG menu) to clear the error message and to continue data
logging at the correct times.
Note:
The instrument can continue operating with a failed battery,
but the correct time will be lost if there are interruptions to
the power supply.
No Flow
Detected
12
The no flow condition is detected when the flow timeout expires
during a delivery. There must not be a period of no flow greater
than the timeout value during the delivery.
Unexpected/
Over Flow
13
The unexpected/over flow condition is detected when the flow
continues longer than the timeout period after the controller has
attempted to stop (or pause) the flow.
Leakage
Detected
14
The leakage condition is detected when an amount greater than the
acceptable total is received without flow being initiated by the
batch controller.
Warning Messages
Description
Value Has Been Set to
Default
You have entered an invalid value for a parameter. Therefore, the
instrument has set the default value.
Содержание 515 BR03
Страница 8: ...viii 515 BR03 15 August 2021...
Страница 10: ...x 515 BR03 15 August 2021...
Страница 16: ...Introduction 6 515 BR03 15 August 2021...
Страница 78: ...Instrument Calibration 68 515 BR03 15 August 2021...
Страница 100: ...90 515 BR03 15 August 2021...
Страница 106: ...96 515 BR03 15 August 2021...