Continental Hydraulics CEM-SD-A Скачать руководство пользователя страница 3

                    Continental Hydraulics Installation Manual                                

Page 3 of 15

CEM-SD-A

CHI 1013477    May 2012

Steps to install and configure a new application:

1. 

Mount the module in a suitable location

2. 

Connect the power supply and valve solenoids

3.

Adjust current range to match valve

4. 

Adjust PWM/Dither to optimize performance of the valve

5. 

Adjust analog input to voltage or current, and scale input to desired system speed

6. 

Adjust ramping (if desired)

7. 

Adjust internal monitor functions (if desired)

6.

Adjust customized current to of valve flow gain (if desired)

All parameters are adjusted using VEA-USB programming cable and CHI-PC Microsoft Windows
application:

Module Mounting Location:

This module is to be mounted in a cabinet for protection from the local environment.
Ensure there is adequate free space around the module to allow for cooling air flow.
This module is designed to snap onto an industry standard 35mm DIN rail.
Do not mount near other modules that emit high power electrical interference, such as motor
controllers and high power contactors.

Power Supply:

This module is designed to operate on DC power from a regulated power supply ranging from 12
to 30 volts.

A 3 amp medium action fuse is recommended in the “+” power supply line.

Adjust MODE to STD or EXP:

Simple parameters may be adjusted while in STD mode.

EXP mode allows for more complex parameter adjustments.

MODE parameter valid options are STD and EXP.  Default is STD.

TS parameter:

TS sets the sample time of the closed loop control system.  Valid settings are from 5 to 30  Units
are msec.  Default is 10.  It is advised to keep this parameter set to 10.

Содержание CEM-SD-A

Страница 1: ...th easy to use software on your Microsoft Windows laptop Control variables are stored in non volatile memory internal to the module All variables can be read by the laptop and reproduced exactly on ot...

Страница 2: ...12 Ground Differential Input on Control Valve 3 20 DC DC 12 to 24v 0v 19 4 Data 32 28 0v 26 27 Data Clock 25 Clock 31 24v supply SSI Digital Feedback Position SSI Feedback Sensor SSI Analog Output 17...

Страница 3: ...n a cabinet for protection from the local environment Ensure there is adequate free space around the module to allow for cooling air flow This module is designed to snap onto an industry standard 35mm...

Страница 4: ...STROKE load distance A A and A B ramping times VELO internally controlled velocity D A and D B Deceleration start point STROKE defines the full motion Valid options are 10 to 10000 Default is 100 Uni...

Страница 5: ...th the VRAMP parameter VRAMP valid values are 1 to 5000 Default is 50 Units are msec Deceleration characteristic is controlled by the CTRL parameter CTRL valid options are LIN SQRT1 and SQRT2 Default...

Страница 6: ...from 5000 to 10000 Default is 10000 Units are 0 01 MIN A and MIN B are adjusted via software for the purpose of deadband elimination A valve with a minimum control point cracking point will give best...

Страница 7: ...pool valve An overlap spool valve will do a better job of holding the load in a static condition An overlap valve can be commanded to go to center In this center condition the valve port to port leaka...

Страница 8: ...ge Source Ground Referenced Voltage PLC Digitial Motion Controller etc Gnd An external position command voltage source must be referenced to ground for proper operation 13 11 24v 3 4 Power Supply Gnd...

Страница 9: ...itor optional Power Supply All analog input signal cables must be shielded Good analog system design requires that all analog signals in an electrically noisy environment be shielded Long wires act li...

Страница 10: ...t C Output of this scaling equation must always be equal to the module native input range 0 to 10v Input can be any voltage within this 10v range The ratio of A B allows for a decimal scaling factor T...

Страница 11: ...rror is corrected the module will resume function without cycling ENABLE If the module has been configured to accept current commands a command value outside of 4 to 20 mA will disable the module and...

Страница 12: ...o START RUN pin 7 digital input START RUN is a digital input that is active high Bringing pin 7 high while holding pin 8 ENABLE high forces the module into closed loop position control mode If RUN is...

Страница 13: ...ystem errors Pin 5 will be pulled low off under the following conditions 1 When ENABLE is removed 2 When SENS is turned on and the input is outside the 4 to 20mA range 3 When other internal errors are...

Страница 14: ...gital feedback INPX parameter This parameter allows the selection of either analog feedback input pins 14 11 or the digital SSI feedback Valid parameters are ANA or SSI Default is ANA SSI OFFSET param...

Страница 15: ...I feedback sensors data may be defined as either GRAY scale or BINary Default is GRAY Parameter monitoring using software The following parameters may be monitored in real time using Windows configura...

Отзывы: