Continental Hydraulics Installation Manual
Page 7 of 20
CEM-BPS-B
CHI 1020813 Jan 2016
Terminal Identification
Connection
Supply
Terminal 3
Power supply connection (see technical data)
Terminal 4
0 V (GND) connection
Connection
Analog signals
Terminal 13
Actual value (X1), signal range 0-10 V or 4-20mA
Terminal 14
Actual value (X2), signal range 0-10 V or 4-20mA
Terminal 11
0 V (GND) connection for analog INPUT signals
Terminal 12
0 V (GND) connection for analog OUTPUT signals
Terminal 15/16
Valve control output signal
Terminal 15/12
Type of OUTPUT signal and polarity (Parameter SIGNAL:U)
Connection
Digital inputs and outputs
Terminal 8
Enable
input:
General enabling of outputs and the application
Terminal 7
START (RUN)
input:
ON:
The Synchronization controller is active
OFF:
The Synchronization controller is not active.
Auto setup Terminal 6 can be used
Terminal 6
AUTO SETUP:
input
The offset error between the two sensors is automatically
measured and stored as a correction value. The input must be
activated for longer than 1 second.
Terminal 5
POLARITY
input:
The polarity of the control loop can be switched on this input
Terminal 1
READY
output:
ON:
The module is enabled with no discernable errors
OFF:
Enable (Terminal 8) is disabled or an error (sensor or
internal error) has been detected
Terminal 2
STATUS
output:
ON:
(CD window) The axis are within the set deviation window
OFF:
(CD window) The axis are outside the set deviation window