Continental Hydraulics Installation Manual
Page 13 of 20
CEM-BPS-B
CHI 1020813 Jan 2016
ENABLE (pin 8) digital input:
ENABLE is a digital input that is active high.
When the ENABLE input is low, there is no output to the valve. All other inputs are also ignored.
If ENABLE is removed during an active motion profile, the output to the valve is instantly brought
to zero.
START (RUN) (pin 7) digital input:
START (RUN) is a digital input that is active high.
Bringing pin 7 high (while holding pin 8 (ENABLE) high), forces the module into closed loop
synchronization control mode.
If RUN is removed during an active motion profile, the output to the valve is ramped to zero.
INPOS (Size of the control deviation window)
Command
Parameters
Unit
Group
INPOS
x
x= 2… 200000
µm
STD
This parameter is entered in µm.
The INPOS command defines a monitoring range for which the INPOS message is generated.
The monitoring window monitors the deviation between the feedback signal X1 and X2. If the
deviation is within the INPOS window, the status output and INPOS LED (Yellow A) will be
activated.
SYS_RANGE (Working stroke)
Command
Parameters
Unit
Group
SYS_RANGE ................................................................................................................................................... x
x= 10… 10000
mm
STD
This command defines the full stroke, which corresponds to 100 % of the input signal. If the
demand is set incorrectly, this leads to incorrect system settings, and the dependent parameters
such as speed and gain cannot be calculated correctly.