19.2

EXAMPLE 1:

In this example, because there is no door to the adjoining room, the volume of the adjoining room may be 
added to the volume of the room with the heater to get a total unconfi ned space.

The total unconfi ned space: 800 + 1200 = 2000 cubic feet.

Maximum BTU/h: 2000x1000 = 40,000 BTU/h
 

 

       50

If there are no more fuel burning appliances within this space then the 30,000 BTU/h input of the appliance is 
suitable to be installed. This also assumes that the construction of this space is not unusually tight.

19.3

EXAMPLE 2:

If in this example a solid door separates Room 1 from Room 2, the volume of Room 2 could not be used. In 
this case the maximum BTU/h would be:

Maximum BTU/h: 800x1000 = 16,000 BTU/h
 

 

        50

This would be considered a confi ned space since it can not support the 30,000 BTU/h input of the appliance 
and it would be necessary to provide adequate combustion and ventilation air to Room 1.

3.3 GAS 

INSTALLATION

30.1A

Installation and servicing to be done by a qualifi ed installer.

A.

   

Move the appliance into position and secure.

B.

 

If equipped with a fl ex connector the appliance is designed to accept a 1/2” gas supply. Without the 
connector it is designed to accept a 3/8” gas supply. The appliance is equipped with a manual shut off 
valve to turn off the gas supply to the appliance.

C.

 

Connect the gas supply in accordance to local codes. In the absence of local codes, install to the 
current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI 
Z223.1 / NFPA 54 in the United States.

D.

 When 

fl exing any gas line, support the gas valve so that the lines are not bent or kinked.

E.

 

The gas line fl ex-connector should be installed to provide suffi cient movement for shifting the burner 
assembly on it’s side to aid with servicing components.

F.

 

Check for gas leaks by brushing on a soap and water solution.  

Do not use open fl ame.

!

WARNING

RISK OF FIRE, EXPLOSION OR ASPHYXIATION. ENSURE THERE ARE NO IGNITION SOURCES SUCH AS 

SPARKS OR OPEN FLAMES.

SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE.

ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT 

WITH THE GLASS DOOR OPENED OR REMOVED. PURGING OF THE GAS SUPPLY LINE SHOULD BE 

PERFORMED BY A QUALIFIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT 

THE BURNER BEFORE CLOSING THE DOOR.  ENSURE ADEQUATE VENTILATION. FOR GAS AND 

ELECTRICAL LOCATIONS, SEE “DIMENSION” SECTION.

ALL GAS CONNECTIONS MUST BE CONTAINED WITHIN THE APPLIANCE WHEN COMPLETE.

HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE TESTING GAS 

LINE AT TEST PRESSURES ABOVE 1/2 PSIG.

VALVE SETTINGS HAVE BEEN FACTORY SET, DO NOT CHANGE.

Содержание CVF36N

Страница 1: ...ely call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by...

Страница 2: ...ETERMINING CONFINED OR UNCONFINED SPACE 7 3 3 GAS INSTALLATION 8 3 4 OPTIONAL WALL SWITCH THERMOSTAT 9 3 5 MOBILE HOME INSTALLATION 9 4 0 FRAMING 10 4 1 MINIMUM CLEARANCE TO COMBUSTIBLES 11 4 2 MINIMU...

Страница 3: ...d hearth guards to protect children from hot surfaces These screens and guards must be fastened to the floor Any safety screen or guard removed for servicing must be replaced prior to operating the ap...

Страница 4: ...install the appliance to the current National Fuel Gas Code ANSI Z223 1 Installation Code which can be obtained from American National Standards Institute Inc or National Fire Protection Association I...

Страница 5: ...the fuel Incomplete combustion results in soot being deposited inside the firebox as well as surfaces outside the appliance If any soot deposits are observed shut off the appliance immediately and ar...

Страница 6: ...CATALYTIC DOOR MAXIMUM HORIZONTAL EXTENSION 2 SEE INSTRUCTION MANUAL FOR GREATER EXTENSIONS ELECTRICAL RATING 115V 0 82AMP 60HZ OPTIONAL FAN KIT GZ550 KT 9700539 WSL 4001657 NGZ 4001658 NAC 4001659 W...

Страница 7: ...pproximately one ounce of water for every 1 000 BTU hr of gas input During the cold weather season indoor humidity levels tend to be low Consequently this water vapour can enhance the living space How...

Страница 8: ...manual shut off valve to turn off the gas supply to the appliance C Connect the gas supply in accordance to local codes In the absence of local codes install to the current CAN CSA B149 1 Installatio...

Страница 9: ...FF switch and replace with the leads from the wall switch millivolt thermostat 50 1 3 1 2 WARNING DO NOT CONNECT EITHER THE WALL SWITCH THERMOSTAT OR GAS VALVE DIRECTLY TO 110 VOLT ELECTRICITY 29 2 Su...

Страница 10: ...TING ENTIRELY OF STEEL IRON BRICK TILE CONCRETE SLATE GLASS OR PLASTERS OR ANY COMBINATION THEREOF ARE SUITABLE MATERIALS THAT ARE REPORTED AS PASSING ASTM E 136 STANDARD TEST METHOD FOR BEHAVIOUR OF...

Страница 11: ...may occur at or after a minimum distance of 2 away from the side of the appliance Thereafter the depth of any protrusions must be of equal to or less than the distance from the side of the appliance u...

Страница 12: ...sure space around and above the appliance must be left unobstructed 4 3 MINIMUM MANTEL CLEARANCES WARNING RISK OF FIRE MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES FAILURE TO COMPLY WIT...

Страница 13: ...re just removed E Install the one piece log set by aligning the two holes on the bottom of the logs with the two locating pins in the firebox Reinstall rod assembly and mesh curtain NOTE PHAZERTM logs...

Страница 14: ...e embers into pieces and place along the front row of ports covering all of the burner area in front of the small logs Care should be taken to shred the embers into thin small irregular pieces as only...

Страница 15: ...ERSAL HARNESS WHEN INSTALLED ENSURE THAT ANY EXCESS WIRE IS CONTAINED PREVENTING IT FROM MAKING CONTACT WITH MOVING OR HOT OBJECTS 51 5 Remove the backing of the logo supplied and place on the screen...

Страница 16: ...e blower does not touch the appliance base or the firebox Attach the connectors from the black and white wires to the thermal switch and secure the thermal switch bracket to the bottom left of the uni...

Страница 17: ...ront of the back log G Turn gas knob counter clockwise to pilot H Depress and hold gas knob while lighting the pilot with the push button ignitor Keep knob fully depressed for one minute then release...

Страница 18: ...y allow 15 to 30 minutes for the final flame colour to be established AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED INSTALLER AIR SHUTTER OPENING VENTURI BURNER ORIFICE 49 1 AIR SHUTTER OPEN...

Страница 19: ...CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing This appliance and its venting...

Страница 20: ...DEPLETION SENSOR SYSTEM LP 3 W680 0004 THERMOPILE 4 W725 0030 NATURAL GAS VALVE 4 W725 0031 PROPANE GAS VALVE 5 W385 0430 CONTINENTAL LOGO 6 W750 0112 20FT OF WIRE 7 GL 664 ONE PIECE LOG SET W135 033...

Страница 21: ...ECTIVE RADIANT PANELS 36 TB336K BEVELLED TRIM KIT 3 COVERS OPENING 37 W X 33 H TEXTURED BLACK 36 TB336AB BEVELLED TRIM KIT 3 COVERS OPENING 37 W X 33 H ANTIQUE BRASS 36 TB336PB BEVELLED TRIM KIT 3 COV...

Страница 22: ...ow Service or replace Oxygen Depletion Sensor System Correct piping and or regulator to provide correct pressure Ensure adequate supply pressure Pilot goes out when the gas knob is released The gas va...

Страница 23: ...and see if pilot flame flutters diminishes or extinguishes especially when main burner ignites Monitor appliance supply working pressure Check if supply piping size is to code Correct all undersized...

Страница 24: ...of the methods described in ANSI Z223 1 NFPA 54 or the applicable local code Not enough ventilation air Increase fresh air supply Use one of the methods described in ANSI Z223 1 NFPA 54 or the applica...

Страница 25: ...ironmental conditions such as rooftops buildings nearby trees hills mountains inadequate vents or ventilation excessive venting configurations insufficient makeup air or negative air pressures which m...

Страница 26: ...26 W415 0298 N 02 29 12 13 0 SERVICE HISTORY 43 1...

Страница 27: ...27 W415 0298 N 02 29 12 44 1 14 0 NOTES...

Страница 28: ...28 W415 0298 N 02 29 12 44 1...

Отзывы: