SYMPTOM

PROBLEM

TEST SOLUTION

Pilot burning; 
no gas to main 
burner; gas 
knob is on ‘HI’; 
wall switch / 
thermostat is on.

Thermostat or switch is 
defective.

 

-

Connect a jumper wire across the wall switch 
terminals; if main burner lights, replace switch / 
thermostat.

Wall switch wiring is 
defective.

 

-

Disconnect wires from valve. Connect a jumper wire 
across terminals 1 & 3; if the main burner lights, 
check the wires for defects and / or replace wires.

Main burner orifi ce is 
plugged.

 

-

Remove stoppage in orifi ce.

Faulty valve.

 

-

Replace.

Pilot will not light.

Out of propane gas.

 

-

Fill the tank.

No spark at pilot burner.

 

-

Check if pilot can be lit by a match.

 

-

Check that the wire is connected to the push button 
ignitor.

 

-

Check if the push button ignitor needs tightening.

 

-

Replace the wire if the wire insulation is broken or 
frayed.

 

-

Replace the electrode if the ceramic insulator is 
cracked or broken.

 

-

Replace the push button ignitor.

No gas at the pilot burner.

 

-

Check that the manual valve is turned on.

 

-

Check the pilot orifi ce for blockage.

 

-

Replace the valve / Oxygen Depletion Sensor 
System.

 

-

Call the gas distributor.

Pilot goes out 
while standing; 
Main burner is in 
‘OFF’ position.

Gas piping is undersized.

 

-

Turn on all gas appliances and see if pilot fl ame 
fl utters, diminishes or extinguishes, especially 
when main burner ignites. Monitor appliance supply 
working pressure.

 

-

Check if supply piping size is to code. Correct all 
undersized piping.

Pilot fl ame is not large 
enough.

 

-

ODS Burner requires checking.

Main burner will 
not light; or is slow 
to light, noisy pilot.

Inlet pressure too high.

 

-

Adjust inlet pressure to ensure maximum 7.0” W.C. 
at gas valve for natural gas and 13.0” W.C. for 
propane.

Pilot fl ame blowing off, 
missing thermopile.

Carbon is being 
deposited on 
glass, logs, 
rocks, media 
or combustion 
chamber.

Air shutter has become 
blocked.

 

-

Ensure air shutter opening is free of lint or other 
obstructions.

Flame is impinging on the 
glass, logs, rocks, media 
or combustion chamber.

 

-

Check that the logs are correctly positioned.

 

-

Check for ceiling or oscillating fans that may be 
infl uencing the fl ame.

 

-

Open air shutter to increase the primary air. See 
“VENTURI ADJUSTMENT” section.

 

-

Check the input rate: check the manifold pressure 
and orifi ce size as specifi ed by the rating plate.

42.4_2_A

ELECTRODE

THERMOCOUPLE

THERMOPILE

PILOT 
BURNER

* Check for ceiling or oscillating fans that maybe infl uencing the fl ame. Ceiling fans or oscillating type fl oor 
fans can cause fl ame impingement if directing air at the appliance. Impinging fl ames will cause soot or carbon 
that may enter into living area. Try reversing ceiling fan or re-directing fl oor fans to prevent sooting.

Содержание CVF36N

Страница 1: ...ely call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by...

Страница 2: ...ETERMINING CONFINED OR UNCONFINED SPACE 7 3 3 GAS INSTALLATION 8 3 4 OPTIONAL WALL SWITCH THERMOSTAT 9 3 5 MOBILE HOME INSTALLATION 9 4 0 FRAMING 10 4 1 MINIMUM CLEARANCE TO COMBUSTIBLES 11 4 2 MINIMU...

Страница 3: ...d hearth guards to protect children from hot surfaces These screens and guards must be fastened to the floor Any safety screen or guard removed for servicing must be replaced prior to operating the ap...

Страница 4: ...install the appliance to the current National Fuel Gas Code ANSI Z223 1 Installation Code which can be obtained from American National Standards Institute Inc or National Fire Protection Association I...

Страница 5: ...the fuel Incomplete combustion results in soot being deposited inside the firebox as well as surfaces outside the appliance If any soot deposits are observed shut off the appliance immediately and ar...

Страница 6: ...CATALYTIC DOOR MAXIMUM HORIZONTAL EXTENSION 2 SEE INSTRUCTION MANUAL FOR GREATER EXTENSIONS ELECTRICAL RATING 115V 0 82AMP 60HZ OPTIONAL FAN KIT GZ550 KT 9700539 WSL 4001657 NGZ 4001658 NAC 4001659 W...

Страница 7: ...pproximately one ounce of water for every 1 000 BTU hr of gas input During the cold weather season indoor humidity levels tend to be low Consequently this water vapour can enhance the living space How...

Страница 8: ...manual shut off valve to turn off the gas supply to the appliance C Connect the gas supply in accordance to local codes In the absence of local codes install to the current CAN CSA B149 1 Installatio...

Страница 9: ...FF switch and replace with the leads from the wall switch millivolt thermostat 50 1 3 1 2 WARNING DO NOT CONNECT EITHER THE WALL SWITCH THERMOSTAT OR GAS VALVE DIRECTLY TO 110 VOLT ELECTRICITY 29 2 Su...

Страница 10: ...TING ENTIRELY OF STEEL IRON BRICK TILE CONCRETE SLATE GLASS OR PLASTERS OR ANY COMBINATION THEREOF ARE SUITABLE MATERIALS THAT ARE REPORTED AS PASSING ASTM E 136 STANDARD TEST METHOD FOR BEHAVIOUR OF...

Страница 11: ...may occur at or after a minimum distance of 2 away from the side of the appliance Thereafter the depth of any protrusions must be of equal to or less than the distance from the side of the appliance u...

Страница 12: ...sure space around and above the appliance must be left unobstructed 4 3 MINIMUM MANTEL CLEARANCES WARNING RISK OF FIRE MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES FAILURE TO COMPLY WIT...

Страница 13: ...re just removed E Install the one piece log set by aligning the two holes on the bottom of the logs with the two locating pins in the firebox Reinstall rod assembly and mesh curtain NOTE PHAZERTM logs...

Страница 14: ...e embers into pieces and place along the front row of ports covering all of the burner area in front of the small logs Care should be taken to shred the embers into thin small irregular pieces as only...

Страница 15: ...ERSAL HARNESS WHEN INSTALLED ENSURE THAT ANY EXCESS WIRE IS CONTAINED PREVENTING IT FROM MAKING CONTACT WITH MOVING OR HOT OBJECTS 51 5 Remove the backing of the logo supplied and place on the screen...

Страница 16: ...e blower does not touch the appliance base or the firebox Attach the connectors from the black and white wires to the thermal switch and secure the thermal switch bracket to the bottom left of the uni...

Страница 17: ...ront of the back log G Turn gas knob counter clockwise to pilot H Depress and hold gas knob while lighting the pilot with the push button ignitor Keep knob fully depressed for one minute then release...

Страница 18: ...y allow 15 to 30 minutes for the final flame colour to be established AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED INSTALLER AIR SHUTTER OPENING VENTURI BURNER ORIFICE 49 1 AIR SHUTTER OPEN...

Страница 19: ...CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing This appliance and its venting...

Страница 20: ...DEPLETION SENSOR SYSTEM LP 3 W680 0004 THERMOPILE 4 W725 0030 NATURAL GAS VALVE 4 W725 0031 PROPANE GAS VALVE 5 W385 0430 CONTINENTAL LOGO 6 W750 0112 20FT OF WIRE 7 GL 664 ONE PIECE LOG SET W135 033...

Страница 21: ...ECTIVE RADIANT PANELS 36 TB336K BEVELLED TRIM KIT 3 COVERS OPENING 37 W X 33 H TEXTURED BLACK 36 TB336AB BEVELLED TRIM KIT 3 COVERS OPENING 37 W X 33 H ANTIQUE BRASS 36 TB336PB BEVELLED TRIM KIT 3 COV...

Страница 22: ...ow Service or replace Oxygen Depletion Sensor System Correct piping and or regulator to provide correct pressure Ensure adequate supply pressure Pilot goes out when the gas knob is released The gas va...

Страница 23: ...and see if pilot flame flutters diminishes or extinguishes especially when main burner ignites Monitor appliance supply working pressure Check if supply piping size is to code Correct all undersized...

Страница 24: ...of the methods described in ANSI Z223 1 NFPA 54 or the applicable local code Not enough ventilation air Increase fresh air supply Use one of the methods described in ANSI Z223 1 NFPA 54 or the applica...

Страница 25: ...ironmental conditions such as rooftops buildings nearby trees hills mountains inadequate vents or ventilation excessive venting configurations insufficient makeup air or negative air pressures which m...

Страница 26: ...26 W415 0298 N 02 29 12 13 0 SERVICE HISTORY 43 1...

Страница 27: ...27 W415 0298 N 02 29 12 44 1 14 0 NOTES...

Страница 28: ...28 W415 0298 N 02 29 12 44 1...

Отзывы: